24
Full-scale and Alarm Set Value Display
・
The full-scale and alarm set values are only displayed. They cannot be changed.
1)
While in gas monitor mode, press the MODE switch on the Detector first. Then
press the UP switch with the magnetic stick within approximately 2 seconds.
2)
The Detector displays
【 】
first, followed by
【 】
.
(This procedure assumes that no operation has been performed after turning
ON the power supply.)
3)
Press the UP or DOWN switch on the Detector with the magnetic stick and
adjust the
value to
【
】
.
4)
Press the ENTER switch on the Detector to start the operation.
5)
When the operation starts, the following values are displayed, and the user
can check the full-scale and alarm set values.
【 】
↓
【 】
↓
【
Full scale
】
↓
【 】
↓
【
Alarm set value
】
6)
After the full-scale and alarm set values are displayed, the Detector will
automatically return to gas monitor mode.
・
Carefully handle and make settings with the magnetic stick because the magnet is very
powerful.
For details, refer to 3. Contents of Package on page 3.