2. Once the through-the-wall thimble
codes are met, simply connect the
chimney pipe to the wall pass-
through connector using #24 ga.
minimum, blued or black steel pipe
as follows:
(a) Maintain 1/4" rise per foot
(horizontal length) from the
appliance to the chimney.
(b) Each section of pipe should fit
into the section below or into
the opening on the stove, for
drip free operation.
(c) Secure each section to each
other using at least three (3)
sheet metal screws or rivets.
(d) Use three (3) screws to connect
pipe to New Buck Corp.
Chimney Connector.
Ceiling Exit—Close Clearance
1. Suspend a plumb bob from the
ceiling above the unit so that the
weight is hanging in the center of
the flue exit. (A small weight on a
string will serve as a plumb bob.)
Mark the ceiling where the string is
suspended to locate the center of
the chimney hole.
2. After locating the center of the
hole, install the ceiling support box,
chimney or chimney connector,
flashing, and rain cap.
3. Next, install a New Buck Corp.
Chimney Connector to the flue of
the heater.
4. Install Double Wall Connector and
chimney system per manufacturer’s
list of tested pipes
Caution:
Because of the high efficiency
and low flue gas temperature,
freestanding catalytic heaters connected
to masonry chimneys with oversized
flue lines may encounter drafting
problems.
CEILING SUPPORT
BOX
SINGLE WALL
PIPE
BUCK STOVE
CHIMNEY CONNECTOR
FIGURE 10
FIGURE 11
15