Example#3
based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
MaxTime
sleeping sleeping
...
0H
15
th
M
30
th
M
45
th
M 1H
1H 10
th
M
1H 25
th
M 1H 40
th
M 1H 55
th
M
2H 10
th
M
Notes :
(1) The device only wakes up and performs data sampling according to MinTime Interval. When it is sleeping, it does not collect
data.
(2) The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the
device reports according to MinTime interval. If the data variation is not greater than the last data reported, the device reports
according to MaxTime interval.
(3) We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too low, the device wakes up
frequently and the battery will be drained soon.
(4) Whenever the device sends a report, no matter resulting from data variation, button pushed or MaxTime interval, another
cycle of MinTime/MaxTime calculation is started.
Wakes up and
collects data
REPORTS 3.6V
Wakes up and collects data
3.5V |3.5-3.6|=0.1
REPORTS 3.5V
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data 3.5V
Does not report
Wakes up and
collects data
3.5V
Does not report
Wakes up and
collects data
REPORTS 3.5V
Wakes up and
collects data
3.6V
Does not report
Users push the button,
REPORTS 3.5V.
Recalculate MaxTime.