
5
5. Data Report
Data report configuration and sending period are as following:
Min. Interval
(Unit:second)
Max. Interval
(Unit:second)
Reportable Change
Current Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
20~65535
Any number between
Min.~65535
Can not be 0.
Report
per Min. Interval
Report
per Max. Interval
Before any configuration is made, the device sends data according to the default configuration.
The device will immediately send a version packet report along with two uplink packets including battery voltage and raw data
of three-phase current.
Default setting:
Maximum time: Max Interval =60 min (3600 s)
Minimum time: Min Interval =60 min (3600 s)
*The interval between min time and max time must be the greater than 20 seconds.
Note:
(1)
The device report interval will be programmed based on the default firmware which may vary.
(2)
If MinTime configuration less than 20 seconds, it will configure 20 seconds.
(3)
R718N360 series would take about 3 seconds for the CT to sample and process the collected value, If the current
changes frequently, the sampling result might be wrong.
Please refer Netvox
LoRaWAN Application Command document
and
Netvox Lora Command Resolver
http://loraresolver.netvoxcloud.com:8888/page/index