5. Data Report   

 

 

Data report configuration and sending period are as following: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. Interval 

(Unit:second) 

Max. Interval 

(Unit:second) 

Reportable Change 

Current Change≥ 

Reportable Change 

Current Change

Reportable Change 

Any number between 

20~65535 

Any number between 

Min.~65535 

Can not be 0. 

Report 

per Min. Interval 

Report 

per Max. Interval 

Before any configuration is made, the device sends data according to the default configuration. 

The device will immediately send a version packet report along with two uplink packets including battery voltage and raw data 

of three-phase current. 

 

Default setting: 

Maximum time: Max Interval =60 min (3600 s) 

Minimum time: Min Interval =60 min (3600 s)                   

*The interval between min time and max time must be the greater than 20 seconds. 

Note:   

(1)

 

The device report interval will be programmed based on the default firmware which may vary. 

(2)

 

If MinTime configuration less than 20 seconds, it will configure 20 seconds. 

(3)

 

R718N360 series would take about 3 seconds for the CT to sample and process the collected value, If the current 

changes frequently, the sampling result might be wrong. 

 

Please refer Netvox 

LoRaWAN Application Command document

 and 

Netvox Lora Command Resolver

 

http://loraresolver.netvoxcloud.com:8888/page/index

 to resolve uplink data. 

 

Summary of Contents for R718N360

Page 1: ... Technology Co Ltd This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of NETVOX Technology The specifications are subject to change without prior notice ...

Page 2: ...2 3 Main Features 3 4 Set up Instruction 4 5 Data Report 5 6 Installation 8 7 Information about Battery Passivation 10 7 1 To determine whether a battery requires activation 10 7 2 How to activate the battery 10 8 Important Maintenance Instruction 11 ...

Page 3: ...nique greatly extend the communication distance It can be widely used in any use case that requires long distance and low data wireless communications For example automatic meter reading building automation equipment wireless security systems industrial monitoring It has features like small size low power consumption long transmission distance strong anti interference ability and so on LoRaWAN LoR...

Page 4: ...reless sensor monitoring and notification system to configure sensors view data and set alerts via SMS text and email optional Available third party platform Actility ThingPark TTN MyDevices Cayenne Low power consumption and long battery life Battery Life 2 Please refer to web http www netvox com tw electric electric_calc html At this website users can find battery life time for variety models at ...

Page 5: ...network to join The green indicator light stays on for 5 seconds joins the network successfully The green indicator light remains off fail to join the network Fail to Join the Network 1 Suggest to remove batteries if the device is not used to save power 2 Suggest to check the device verification information on the gateway or consult your platform server provider Function Key Press the function key...

Page 6: ...ery voltage and raw data of three phase current Default setting Maximum time Max Interval 60 min 3600 s Minimum time Min Interval 60 min 3600 s The interval between min time and max time must be the greater than 20 seconds Note 1 The device report interval will be programmed based on the default firmware which may vary 2 If MinTime configuration less than 20 seconds it will configure 20 seconds 3 ...

Page 7: ... 1bytes Fixed 0x00 1 Configure device parameters MinTime 1min MaxTime 1min CurrentChange 100mA Downlink 01CA003C003C0000006400 The device returns 81CA000000000000000000 Configuration successful 81CA010000000000000000 Configuration fail 2 Read device configuration parameters Downlink 02CA000000000000000000 The device returns 82CA003C003C0000006400 current device parameters Example for MinTime MaxTi...

Page 8: ... recommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter resulting from data variation button pushed or MaxTime interval another cycle of MinTime MaxTime calculation is started Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 ...

Page 9: ... value of R718N360 is 165806 k 165806 49950 3 3194394 After obtaining the conversion coefficient k use R718N360 to measure the target load The current value of the target load R718N360 read value k Example R718N360 reads the value 333162 The current value of the target load 333162 3 3194394 100366 9475032mA Installation Diagram Screw Fixation Screw Fixation R718N360 Wire to be detected Wire to be ...

Page 10: ...o avoid affecting the wireless transmission of the device 2 The Wireless 3 Phase Current Meter Interface R718N360 samples the current according to MinTime If the current value sampled this time relatively exceeds the set value the default is 100mA more than the current value reported last time the device will immediately report the current value sampled this time If the current variation does not ...

Page 11: ...y passivation may also lead to voltage delay when the batteries are put into operation and our devices may not work correctly in this situation As a result please make sure to source batteries from reliable vendors and the batteries should be produced within the last three months If encountering the situation of battery passivation users can activate the battery to eliminate the battery hysteresis...

Page 12: ...melt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicate structures Do not clean the device with strong chemicals detergents or strong detergents Do no...