Data report configuration and sending period are as following

 

Min Interval 

(Unit: second) 

Max Interval 

(Unit: second) 

Reportable Change 

Current Change ≥ 

Reportable Change 

Current Change 

 

Reportable Change 

Any number between 

1~65535 

Any number between 

1~65535 

Can not be 0 

Report per Min Interval  Report per Max Interval 

 

Example of ConfigureCmd 

FPort

0x07 

Bytes 

Var (Fix =9 Bytes) 

 

CmdID 

DeviceType 

NetvoxPayLoadData 

CmdID

– 1 bytes   

DeviceType

– 1 byte – Device Type of Device 

NetvoxPayLoadData

– var bytes (Max=9bytes) 

 

(1)

 

Configure R311K device parameter MinTime = 1min

MaxTime = 1min

BatteryChange = 0.1v 

     Downlink

  019E003C003C0100000000 

     Device return

 

            819E000000000000000000 (configuration success) 

            819E010000000000000000 (configuration failure) 

(2)

 

Read R311K device parameter 

      Downlink

  029E000000000000000000 

     Device return

 

            829E003C003C0100000000 (device current parameter) 

 

Description 

Device 

CmdID 

Device

Type 

NetvoxPayLoadData 

ConfigReport

Req 

R311K 

0x01 

0x9E 

MinTime 

(2bytes Unit: s) 

MaxTime 

(2bytes Unit: s) 

BatteryChange 

(1byte Unit:0.1v) 

Reserved 

(4Bytes, Fixed 0x00) 

ConfigReport

Rsp 

0x81 

Status (0x00_success) 

Reserved (8Bytes, Fixed 0x00) 

ReadConfigR

eportReq 

0x02 

Reserved (9Bytes, Fixed 0x00) 

ReadConfigR

eportRsp 

0x82 

MinTime 

(2bytes Unit :s) 

MaxTime 

(2bytes Unit: s) 

BatteryChange 

(1byte Unit:0.1v) 

Reserved 

(4Bytes, Fixed 0x00) 

Summary of Contents for R311K

Page 1: ...document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in pa...

Page 2: ...1 Table of Content 1 Introduction 2 2 Appearance 2 3 Main Feature 3 4 Set up Instruction 3 5 Data Report 5 6 Installation 8 7 Important Maintenance Instruction 9...

Page 3: ...sumption Compared with other communication methods LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low data wireless communic...

Page 4: ...at different configurations 4 Set up Instruction On Off Power on Insert batteries user may need a screwdriver to open Insert 2 x 3V CR2450 button batteries into the battery slot in the correct direct...

Page 5: ...ation information on the gateway or consult your platform server provider Function Key Press and hold for 5 seconds Restore to the original setting Turn off The green indicator flashes 20 times succes...

Page 6: ...ire circumference The initial state of the device is vertical placement When the tilt angle any direction changes more than 45 45 180 an tipping alarm will be issued immediately Device Tilt 1 Device R...

Page 7: ...Time 1min MaxTime 1min BatteryChange 0 1v Downlink 019E003C003C0100000000 Device return 819E000000000000000000 configuration success 819E010000000000000000 configuration failure 2 Read R311K device pa...

Page 8: ...h M Wake up and collects data REPORTS 2 8V Wakes up and collects data REPORTS 2 8V Wakes up and collects data REPORTS 2 8V Wakes up and collects data 2 8V Does not report Wakes up and collects data 2...

Page 9: ...e MinTime Interval value too low If the MinTime Interval is too low the device will wake up frequently and the battery will be drained soon 4 When the device sends a report no matter the data changes...

Page 10: ...stic parts Do not store in excessive cold place Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device...

Reviews: