Grounding requirement
•
Connect the ground wire to the grounding hardware on the device. Ground resistance should be
no more than 1
Ω
.
Grounding is essential for device’s functionality, surge and electronic interference
protection
•
Keep proper contact with the metal housing of the device
•
Grounding wire must be made out of copper and as thick and short as possible
•
Make sure the two ends of grounding wire conduct electricity and are not rusty
•
It is prohibited to use any other devices as a part of grounding electric circuit
•
All racks should be connected with a protective copper strip. Ground loops should be avoided
•
Grounding wire’s contact area with the rack should be no less than 25mm
2