Installation
9
Installation and Programming manual
EXTRA
CONNECTIONS
Connection of the LED terminal to an open-collector output, will
allow management of the STATUS and PRG LEDs, flasher and horn
directly from the intrusion-control panel (as programmed).
Connection of the FAULT and TAMPER outputs to a terminal on the
intrusion control panel allows signalling of the associated events.
This function allows fault and tamper signals to be transmitted
without activating the visual-signalling components.
2-3
Battery connections
This device requires a 12V, 2.1Ah battery (not included), which must
be connected by means of the respective wires (
Table 3, E
) . Take
care to respect the battery polarity during the installation phase
(red=positive; black=negative).
The battery-efficiency test will run 60 minutes after installation and
every 10 minutes thereafter. In the event of an alarm, the battery
test will be delayed by 60 minutes.
Failure of the battery-efficiency test will generate the respective
signal (
Table 6, Battery inefficient
). If the battery voltage drops
below 11V during an alarm event, the horn will deactivate
automatically, however, all other signalling will continue until the
voltage drops below 10V.
All functions will be re-established when the battery voltage restores
to 12V.