Neptronic TUCB Series User Manual Download Page 6

 

 Universal Wall-Mount Controller 

Modbus Communication Module User Guide

 

 

www.neptronic.com 

page | 6 

Register 

Index 

Description 

Data Type 

Range 

Writable 

400

34

 

Binary output - 6 relays output status. 

Bit String 

[B6-B15]

Reserved

 

 
B0: Binary Output 1 
0 = Open, 1 = Close 
 
B1: Binary Output 2 
0 = Open, 1 = Close 
 
B2: Binary Output 3 
0 = Open, 1 = Close

 

B3: Binary Output 4

 

0 = Open, 1 = Close 

 

B4: Binary Output 5 
0 = Open, 1 = Close 
 
B5: Binary Output 6

 

0 = Open, 1 = Close 

400

35

 

System command. 

Bit String 

[B2, B6, B9 - B15]

Reserved 

 

B0: Cfg_ServiceDisplayAddress 
0 = Normal, 1 = Display address on LCD 
 
B1: Cfg_CoolingRampLock 
0 = Off, 1 = On 
 
B3: Cfg_HeatingRamp1Lock
  
0 = Off, 1 = On 

B4: Cfg_HeatingRamp2Lock  
0 = Off, 1 = On 
 
B5: Cfg_ChangeOverRampLock  
0 = Off, 1 = On 
 
B7: Cfg_HumidifyRampLock 
0 = Off, 1 = On 

 

B8: Cfg_DehumidifyRampLock 
0 = Off, 1 = On

 

400

36

 

System mode status. 

Unsigned 

1 = Auto [Register 400

74

 allows Auto Mode (1 or 5)] 

2 = Heating [Register 400

74

 allows Heating Mode (1, 2 or 4)] 

3 = EMH [Register 400

41

 Bits 2 and 1 = On and Enable (1) and  

Register 400

74

 allows Heating Mode (1, 2 or 4)] 

4 = Cooling [Register 400

74

 allows Cooling Mode (1, 3 or 4)] 

5 = Fan [Register 400

40

 Bit 12 = Advanced (1) and Bit 13 = Enable] 

6 = Off [Register 400

39

 Bit 8 = Enable (0)] 

400

37

 

Fan speed selection by user. 

Unsigned 

1 = Auto, 2 = Low, 3 = Med, 4 = High 

400

38

 

Temperature setpoint in occupancy or day mode. 

Signed 

Scale 10

 

Unit: ºC/ºF, Range: min to max setpoint, 

Value x 10 (e.g. 18°C = 180)

 

 

 

 

 

 

 

Summary of Contents for TUCB Series

Page 1: ...Wall Mount Controller TUCB TUHB Series Modbus Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humidity S...

Page 2: ...s The controller Modbus server supports the following exception codes o Illegal data address o Illegal data value o Slave device busy Serial Line The controller Modbus over serial line uses RTU transm...

Page 3: ...Unsigned Scale 100 0 9600 19200 38400 or 57600 0 Auto Baud Rate Detection Value 100 e g 38400 baud 384 W 40002 Communication port configuration Unsigned 1 No parity 2 Stop bits 2 Even parity 1 stop bi...

Page 4: ...3 Changeover temperature sensor reading Signed Scale 100 Unit C F Range 40 C to 100 C or 40 F to 212 F Value x 100 e g 23 C 2300 or 33 F 3300 RO 40014 Control temperature reading Signed Scale 100 Unit...

Page 5: ...Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40026 Actual cooling demand of ramp 2 Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40027 Actual changeover demand U...

Page 6: ...f 1 On B3 Cfg_HeatingRamp1Lock 0 Off 1 On B4 Cfg_HeatingRamp2Lock 0 Off 1 On B5 Cfg_ChangeOverRampLock 0 Off 1 On B7 Cfg_HumidifyRampLock 0 Off 1 On B8 Cfg_DehumidifyRampLock 0 Off 1 On W 40036 System...

Page 7: ...tPointLock 0 Off 1 On B4 Cfg_ProgramModeLock 0 Off 1 On B7 AL_FreezeProtection 0 Off 1 On B8 Cfg_UserSysOffModes 0 Enable 1 Disable B9 Cfg_KeyPadBottomLeftLock 0 Off 1 On B10 Cfg_KeyPadUpperLeftLock 0...

Page 8: ...Output2Direction 0 Direct 1 Reverse B8 Cfg_BinaryOutput3Direction 0 Direct 1 Reverse B9 Cfg_BinaryOutput4Direction 0 Direct 1 Reverse B10 Cfg_BinaryOutput5Direction 0 Direct 1 Reverse B11 Cfg_BinaryOu...

Page 9: ...0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or 2 F 20 W 40051 Heating proportional band for ramp 2 Unsigned Scale 10 Unit depends on system unit 0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or...

Page 10: ...d Scale 1 Unit Minutes Range 0 to 15 minutes Value x 1 e g 10 mins 10 W 40067 NSB override delay in minutes Unsigned Scale 1 Unit Minutes Range 0 to 180 minutes Value x 1 e g 100 mins 100 W 40068 Unoc...

Page 11: ...ch binary input 16 OverHeat binary input 17 Selector switch binary input 18 Humidity sensor 0 10V W 40079 External temperature sensor offset correction Signed Scale 100 Unit depends on system unit Ran...

Page 12: ...3 V 30 W 40092 Position of CH1 AO output while heating Unsigned Scale 1 Unit Range 0 to 100 Value x 1 e g 10 10 W 40093 Ramp to control binary output 1 Unsigned 1 Off 2 Changeover with fan 3 Cooling...

Page 13: ...on percentage for contact BO3 Unsigned Scale 1 Unit Range 0 to BO3closepos 4 Value x 1 e g 20 20 W 40105 Ramp to control binary output 4 Unsigned 1 Off 2 Changeover with fan 3 Cooling 1 with fan 4 Coo...

Page 14: ...s Value x 1 e g 5 5 mins W 40115 Close position percentage for contact BO6 Unsigned Scale 1 Unit Range 15 to 80 Value x 1 e g 20 20 W 40116 Open position percentage for contact BO6 Unsigned Scale 1 Un...

Page 15: ...pancy or day mode Unsigned Scale 10 Unit RH Limited by min max humidity setpoint Value x 10 e g 20 RH 200 W 40126 Dehumidification setpoint RH in unoccupied or night mode Unsigned Scale 10 Unit RH Ran...

Page 16: ...le 40135 Minimum output voltage required for cooling for the 6 way valve Unsigned Scale 100 Unit V Range 0 to 11 V Value x 100 e g 2V 200 W 40136 Minimum output voltage required for heating for the 6...

Page 17: ...Notes...

Page 18: ......

Page 19: ......

Page 20: ...eau blvd Montreal Qc H4N 1R6 Canada neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Easter...

Reviews: