Neptronic TRT2422 Specification And Installation Instructions Download Page 2

Rooftop Thermostat Controller

Specification and Installation Instructions

 

www.neptronic.com

 

 

Page | 2

 

Terminal Identification 

Terminal Description 

Specifications 

C Common 

R

 

24Vac  

22 to 26Vac 50/60Hz 

W1 

Heating Stage 1 

Dry contact, 24Vac, 1A max, 3A in-rush 

W2 

Heating Stage 2 

Dry contact, 24Vac, 1A max, 3A in-rush 

Y1 

Cooling Stage 1 

Dry contact, 24Vac, 1A max, 3A in-rush 

Y2 

Cooling Stage 2 

Dry contact, 24Vac, 1A max, 3A in-rush 

Fan 

Dry contact, 24Vac, 1A max, 3A in-rush 

DI 

Digital Input 

Dry contact (Filter, Service or Air Flow Switch) 

TS 

External Control Temperature Sensor Input 

Thermistor 10K

, Type III. Cannot be used at the same time as the internal control 

sensor. Select the sensor from the thermostat menu. 

C Common 

DS 

Temperature Display Sensor Input 

Thermistor 10K

, Type III. This temperature input performs no control and will only 

display the temperature. 

PCB 

We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only 
Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. 
 

 

 

Jumpers Description

JP2 

Thermostat Mode 

A&B = RUN:    

The thermostat function in Operation Mode (Default) 

B&C = PGM:    

The thermostat is in Programming Mode 

JP4 

Universal Input (pin #16) 

A&B = Low Limit:  Must be set to this position (Thermistor 10K 

, Type III) (Default) 

B&C = N/A:  

 

Not applicable  

TB1

JP2

P

G

M

RUN

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

JP4

24Vac

(R)

COM

 

(C)

W1 

A
B
C

A
B
C

Temperature 
Sensor

2

W2 

Y1

Y2

G

COM

Ext Temp

Display Temp

DI

DI Digital Input 

(Input 13)

Filter: message only
Service: message only
Air Flow Switch: stops unit

External Control Temperature Sensor 

(Input 14)

WARNING! The external control sensor cannot be 
used at the same time as the internal control sensor. 
Select the sensor from the thermostat menu.

Temperature Display Sensor

 (Input 16)

This temperature input performs no control 
and will only display the temperature.

Summary of Contents for TRT2422

Page 1: ...ion Backlit LCD with simple icon and text driven menus Multi level lockable access menu and setpoint Selectable Fahrenheit or Celsius scale Removable connectors TRT2422 Applications 2 Heat 2 Cool Supp...

Page 2: ...ongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products This precaution will prevent interference with and or...

Page 3: ...sed in this Manual Temperature Heating Cooling Fan Schedule Mode Timer clock W1 Heating Stage 1 W2 Heating Stage 2 Y1 Cooling Stage 1 Y2 Cooling Stage 2 User Control 1 Inside Temp Sensor Offset Range...

Page 4: ...Default Range Increment 0 3 C 0 6 F 0 to 5 0 C 0 to 10 F 0 1 C 0 2 F Select the desired dead band value of the heating ramp The heating symbol is also displayed 6 Control Dead Band Cooling Default Ra...

Page 5: ...p 10 Contact automatically opens at 0 of the demand 13 Select W1 Direct Reverse W1 Default Range dir Direct dir Direct or rEV Reverse Select the direction for the W1 output signal Set dir Direct for n...

Page 6: ...the demand 20 Select Y1 open Percent Y1 Default Range Increment 20 of demand 0 to 80 range is limited by the close value of step 19 minus 10 5 Select the percentage at which you want Y1 to open at of...

Page 7: ...symbol is also displayed Temperature Sensor Settings 28 Extern Sensor Temp Default Range OFF OFF t10 0 external temperature sensor 10 0 K at input 14 Select the temperature sensor that will be used b...

Page 8: ...used to notify that service is required When activated Service and the symbol are displayed All control modes continue to function Airf The input is used to connect an air flow sensor When activated...

Page 9: ...es 4 enter year Default Range Increment Selection 2010 2010 to 2099 1 Year Select the year 5 enter month Range Increment Selection 01 to 12 January to December 1 month Month Select the month 6 enter d...

Page 10: ...event 1 cooling setpnt Default Range Increment Display 22 C 72 F 10 to 40 C 50 to 104 F Off 0 5 C 1 F MO Select the desired cooling temperature setpoint for the duration of Event 1 The minimum value i...

Page 11: ...ontinue Event 1 4 Events Day If the 4 events per day option was selected at step 9 16 e1 Default Range Increment Display 06 00 00 00 to Monday Event 2 start time 15 minutes 15 minutes MO E1 Set the st...

Page 12: ...t the desired heating temperature setpoint for the duration of Event 2 The maximum value is restricted by the cooling setpoint of Event 2 at step 20 Event 3 4 Events Day If the 4 events per day option...

Page 13: ...copy Monday s schedule to Tuesday Wednesday Thursday and Friday 28 copy schedul Default Range No No Yes selected day If you do not want to copy a schedule select NO The currently configured days appea...

Page 14: ...ked Yes No Select No to allow the user to change control modes Select Yes to lock the control mode to the user A lock symbol appears to indicate that the control mode is locked 32 quit Default Range Y...

Page 15: ...the arrow keys while the temperature is displayed If the setpoint adjustment has been locked Step 29 on page 13 the lock symbol appears Room temperature Appears if setpoint adjustment is locked Change...

Page 16: ...y on OFF Override Setpoint This function is only available if you have set the used time schedule option to Yes at Step 7 on page 9 When the schedule is triggered the thermostat uses the setpoints def...