Neptronic TFCB24F3XY2 User Manual Download Page 8

TFxB Series Thermostat Controller

 

Page  | 7 

 

Objects Table 

The TFxB24 Thermostat series of controllers use the following BACnet

®

 object table. The 

type

 is the BACnet

®

 

Object type, the 

instance

 is the BACnet

®

 Object.  Together the 

type

 and 

instance

 form the BACnet

®

 

Object_Identifier for an object according to the following C-language algorithm: 
 

 

object_identifier=(unsigned long)((unsigned long)

type

<<22)+

instance

 

 

ID

8

 Name 

Writable  
Property 

TF

C

B

24F

3XYZ

1

 

TF

C

B

24F

3XY

2

 

TF

H

B

24F

3XYZ

1

 

TF

H

B

24F

3XYZ

2

 

TF

C

B

24

P

3

-OE

1

 

TF

H

B

24

P

3

-OE

1

 

TF

H

B

24

P

3

-OE

2

 

Notes 

AI.1 

Intern.Temper. 

Out of service 

x x

x x

x

x

x

0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF 

AI.2 

Extern.Temper. 

Out of service

x x   

x

x

x

x

0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF 

AI.3 

ChangeOverTemper. 

Out of service

x x  x x

x

x

x

0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF 

AI.4 

Intern.Humidity 

Out of service

 

 

 

 

x

 

 

x

5-95%RH, Resolution 0.1%RH 

AI.9 

Extern.Humidity 

Out of service

    x  

  x

 

5-95%RH, Resolution 0.1%RH 

AV.1 

ControlTemper. 

Out of service

 

x x

x x

x

x

x

0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF 

AV.2 

HeatingDemand 

Out of service

 

x x  x x

x

x

x

0-100%, Resolution 0.1% 

AV.3 

CoolingDemand 

Out of service

 

x x

x x

x

x

x

0-100%, Resolution 0.1% 

AV.4 

FanDemand 

Out of service

x x  x x

x

x

x

0-100%, Resolution 0.1% 

AV.5 

Intern.Temper.Offset Present 

Value 

x x  x x

x

x

x

± 5.0ºC, Resolution 0.1ºC 

AV.6 

Extern.Temper.Offset Present 

Value

x x   

x

x

x

x

± 5.0ºC, Resolution 0.1ºC 

AV.7 

Temper.SetPointOcc. Present 

Value

 

x x  x x

x

x

x

AV.8 to AV.9, Resolution 0.5ºC/1ºF 

AV.8 

Min.SetPointOcc. Present 

Value

 

x x

x x

x

x

x

0 to AV.9, Resolution 0.5ºC/1ºF 

AV.9 

Max.SetPointOcc. Present 

Value

x x  x x

x

x

x

AV.8 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF 

AV.10 

Temper.SetPointCoolNoOcc. Present 

Value

 

x x

x x

x

x

x

AV.11 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF 

AV.11 

Temper.SetPointHeatNoOcc. Present 

Value

x x  x x

x

x

x

10.0ºC or 50ºF to AV.10, Resolution 0.5ºC/1ºF 

AV.12 

CoolingProp.Band Present 

Value

x x  x x

x

x

x

0.5-5ºCor 1-10ºF, Resolution 0.5ºC/1ºF 

AV.13 

HeatingProp.Band Present 

Value

 

x x  x x

x

x

x

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.14 

CoolingDeadBand Present 

Value

x x  x x

x

x

x

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.15 

HeatingDeadBand Present 

Value

  x x  x x

x

x

x

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.16 

FanTimeOutDelay Present 

Value

 

x x  x x

x

x

x

0-15 minutes, Resolution 1 minute 

AV.17 

Heat/CoolVoltageMin.2pipes Present 

Value

 

x x

x x

x

x

x

0 Volt to AV.20, Resolution 0.1 Volt 

AV.18 

CoolingVoltageMin.4pipes Present 

Value

x x  x x

x

x

x

0 Volt to AV.21, Resolution 0.1 Volt 

AV.19 

HeatingVoltageMin.4pipes  

For TFHB24P3-OE1 and TFHB24P3-OE2 

  Heating4PipesOrHumid.Volt.Min. 

Present Value

 

x x  x x

x

x

x

0 Volt to AV.22, Resolution 0.1 Volt 

AV.20 

Heat/CoolVoltageMax.2pipes Present 

Value

  x x  x x

x

x

x

AV.17 to 10.0 Volt, Resolution 0.1 Volt 

AV.21 

CoolingVoltageMax.4pipes Present 

Value

 

x x  x x

x

x

x

AV.18 to 10.0 Volt, Resolution 0.1 Volt 

AV.22 

HeatingVoltageMax.4pipes  

For TFHB24P3-OE1 and TFHB24P3-OE2 

  Heating4PipesOrHumid.Volt.Max. 

Present Value

 

x x  x x

x

x

x

AV.19 to 10.0 Volt, Resolution 0.1 Volt 

AV.23 

ChangeOverSetPoint Present 

Value

 

x x  x x

x

x

x

10-40ºC or 50-104ºF, Resolution 0.5ºC/1ºF 

AV.25 

FanDampingFactor Present 

Value

x x  x x

x

x

x

0-10 seconds, Resolution 1 second 

AV.26 

Int.TimeFactor Present 

Value

x x  x x

x

x

x

0-250 seconds, Resolution 5 seconds 

AV.27 

CoolingAntiCycleDelay Present 

Value

 

x x  x x

x

x

x

0-15 minutes, Resolution 1 minute 

AV.28 

Loc.Heat.Demand 

Out of service

 

x

x x

x

x

x

0-100%, Resolution 0.1% 

AV.29 

Loc.Heat.Prop.Band Present 

Value

 

x   x x

x

x

x

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.30 

Loc.Heat.DeadBand Present 

Value

 

x

x x

x

x

x

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.31 

FloatingMotorTiming Present 

Value

x   x x

x

x

x

15-250 seconds, resolution 5 seconds 

AV.32 

Loc.Heat.VoltageMin. Present 

Value

 

x

x x

x

x

x

0 Volt to AV.33, Resolution 0.1 Volt 

AV.33 

Loc.Heat.VoltageMax. Present 

Value

x   x x

x

x

x

AV.32 to 10.0 Volt, Resolution 0.1 Volt 

AV.34 

FanVoltageMin. Present 

Value

x   x x

x

x

x

0 Volt to AV.35, Resolution 0.1 Volt 

AV.35 

FanVoltageMax. Present 

Value

  x  

x x

x

x

x

AV.34 to 10.0 Volt, Resolution 0.1 Volt 

AV.36 

Dehumid.Demand 

Out of service 

    x x

  x

x

0-100%, Resolution 0.1% 

AV.37 

HumiditySetPoint Present 

Value 

x x

x

x

10.0-65.0%RH, Resolution 0.5%RH 

AV.38 

Intern.HumidityOffset Present 

Value 

 

 

 

x

 

 

x

± 5.0%RH, Resolution 0.1%RH 

AV.39 

NoOcc.OverrideDelay Present 

Value

x x

x x

x

x

x

0-180 minutes, Resolution 15 minutes 

AV.40 

HumidityControlRamp Present 

Value 

    x x

  x

x

3.0-10.0%RH, Resolution 0.5%RH 

AV.41 

Humidif.Demand 

Out of service 

 

 

 

 

 

x

x

0-100%, Resolution 0.1% 

AV.42 

CoolingDemand2 

Out of service

 

 

 

 

x

x

x

0-100%, Resolution 0.1% 

AV.43 

CoolingProp.Band2 Present 

Value

 

 

 

 

x

x

x

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.44 

CoolingDeadBand2 Present 

Value

 

x

x

x

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.45 

Extern.HumidityOffset Present 

Value 

    x  

  x

 

± 5.0%RH, Resolution 0.1%RH 

                                                      

8

 ID is equal to ObjectType.Instance 

Summary of Contents for TFCB24F3XY2

Page 1: ...TFxB Series Thermostat Controller BACnet Communication Module User Guide TFxB SERIES BACNET USER GUIDE TFxB24 Bacnet 121026 EUA doc...

Page 2: ...xB Series Thermostat Controller 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Propertie...

Page 3: ...Started section on page 3 For more information on the thermostat menu please refer to the thermostat controller s Specification Installation Manual for more details BIBB Support The thermostat control...

Page 4: ...e can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name Name of devic...

Page 5: ...sed on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 oth...

Page 6: ...APDU_Retries Always 0 Protocol_Services_Supported Always 0x00 0x09 0x40 0x00 0x60 i e a bitstring in BACnet order Protocol_Object_Types_Supported Always 0x00 0xB4 0x80 0x10 i e a bitstring in BACnet o...

Page 7: ...hermostat controllers offer the use of the Out of Service writable property When set to true this property disconnects the object from the physical input enabling you to input other values This could...

Page 8: ...geMin 2pipes Present Value x x x x x x x 0 Volt to AV 20 Resolution 0 1 Volt AV 18 CoolingVoltageMin 4pipes Present Value x x x x x x x 0 Volt to AV 21 Resolution 0 1 Volt AV 19 HeatingVoltageMin 4pip...

Page 9: ...x x 0 Off 1 On MSV 1 UniversalInputFunction 12 Present Value x x x x x 1 Off 2 Extern Sensor States of TFCB24F3XY2 product States available if BV 5 is set to 2Pipe 1 ChangeOverSensor 2 Ch Ov ContactNo...

Page 10: ...Cooling 1 Cooling 2 Fan 3 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heating 1 Heating 2 Fan 3 Off only if BV 3 is set to Enable States available if MSV 4 is set to HeatingO...

Page 11: ...m Heat States available if BV 5 is set to 4Pipe except for OE1 version 1 Off States available if BV 5 is set to 4 Pipe in OE1 version 1 Off 2 Extern Sensor MSV 13 OccupancyMode 14 Present Value x x x...

Page 12: ...treal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service Fax 514 333 1091 Business hours from Monday to Friday 8 00am to 5...

Reviews: