SKS4 Steam to Steam Humidifier
Modbus Communication Module User Guide
Page | 5
Protocol
Base
Holding
Register
Description
Data Type
Units, Limits, State Texts
Writable
Default
Value
6013
40
6014
HRL Humidity
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 1% RH = 100)
RO
0% RH
6014
40
6015
Board Temperature
Unsigned
Scale 100
Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F
Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)
RO
0°C or 32°F
6015
40
6016
Power Output Feedback
Unsigned
Scale 100
Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
RO
0%
6016
40
6017
Water Level
Unsigned
Scale 10
Unit: %, Range: 0% to 120%
Value x 10 (e.g. 10% = 100)
RO
78%
6017
40
6018
Water Probe Low Pos Reading
Unsigned
Scale 1
Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
RO
30000Hz
6018
40
6019
Water Probe High Pos Reading
Unsigned
Scale 1
Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
RO
30000Hz
6019
40
6020
Water Probe Abs Low Pos Reading
Unsigned
Scale 1
Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
RO
30000Hz
6020
40
6021
Water Probe Abs High Pos Reading
Unsigned
Scale 1
Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)
RO
30000Hz
6021
40
6022
Room RH Network Reading
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
RO
0% RH
6022
40
6023
Room RH Setpoint
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
W
40% RH
6023
40
6024
Room RH Unoccupied Setpoint
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
W
30% RH
6024
40
6025
Room RH Vacant Setpoint
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
W
20% RH
6025
40
6026
Room Demand
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10%
RH
= 1000)
RO
0% RH
6026
40
6027
Supply High Limit Network Reading
Unsigned
Scale 100
Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
W
0% RH