HRO20 

Specification & Installation Instructions

 

 

 

Step Display 

Description 

Values 

16 

 

Minimum voltage of AO4 output:

Display shows 

“min vdc analog ao4 output”

 and the value of the 

minimum voltage of the signal “

0.0

” for 0 to 10 Vdc or “

2.0

” for 2 to 10 

Vdc. Humidify symbol is also displayed. 
 
Please select the desired value of the minimum voltage of AO4 output. 

 

Range: 0.0 or 2.0 Volt 

Default value: 0.0 Volt

 

17 

 

Set AI1 input signal:

 

Display shows 

“select AI1 input signal”

.

 

 

Select which signal you want for AI1 input. 
 
You can choose: 

 

OFF

 (input not used), 

 

EHS.0 

(external humidity sensor 0-10 Vdc), 

 

EHS.2

 (external humidity sensor 2-10 Vdc), 

 

SPS

 (external set point from Neptronic humidifier), 

 

HIL.0

 (high limit 0-10 Vdc), 

 

HIL.2

 (high limit 2-10 Vdc). 

 

If you have selected OFF or SPS, go directly to step #20. 
 
Note: If SPS is selected, the dehumidify set point will be disabled.

 

 

 

 

 

 

Default value: OFF

 

18 

%RH

 

External humidity sensor offset calibration:

  

(If ‘’

EHS.0

’’, ‘’

 EHS.2

’’, ‘’

HIL.0

’’ or ‘’

HIL.2

’’ has been selected at step #17)

 

Display shows 

“extern humidty sensor offset”

 

and relative humidity 

percentage read by external humidity sensor. Humidify symbol is also 
displayed. 
If the sensor is not connected or short circuited, the display shows 

Eror

.

You can adjust the calibration of the sensor by comparison with a known 
humidistat. For example if humidistat has been installed in an area where 
humidity is slightly different than the room typical humidity. 

Range: 10 to 90%RH 
  

(max. offset ± 5%) 

Increment: 0.1%RH 
0.0%RH = no humidity sensor 

19 

%RH

 

Adjust high limit set point:

  

(If ‘’

HIL.0

’’ or ‘’

HIL.2

’’ has been selected at step #17)

 

 
Display shows 

“adjust setpnt high limit”

 and the high limit set point. 

Select the desired high limit humidity set point; this one should be within 
the high limit range. 

Set point range: 10 to 90%RH 
Increment: 1%RH 

Default value: 80%RH 

20 

 

Set AI2 input signal:

 

Display shows 

“select AI2 input signal”

Select which signal you want for AI2 input. 
 
You can choose: 

 

OFF

 (input not used), 

 

Wts

 (Window Temperature Sensor 10K

), 

 

OtS

 (Outside Temperature Sensor 10K

). 

If you have selected OFF, go directly to step #1. 

 

 

Default value: OFF

 

21 

C

 

External temperature sensor calibration:

  

(If ‘’

WtS

’’ or ‘’

EtS

’’ has been selected at step #20)

 

Display shows 

“extern temper sensor offset”

 and the temperature read 

by the external temperature sensor (if connected on the selected input). 
If the sensor is not connected or short circuited, the display shows 

Eror

You can adjust the calibration of the external sensor by comparison with a 
known thermometer. 

Range: -30 to 90ºC [-22 to 194ºF] 
  

(max. offset ± 5ºC) 

Increment: 0.1ºC [0.2ºF] 

22 

 

Window temperature sensor compensation factor:

  

(If ‘’

WtS

’’ has been selected at step #20)

 

Display shows 

“window temper sensor compens”

 and the value of the 

compensation factor. 
You can adjust the compensation factor to avoid condensation on the 
window. 
 
The lower the compensation factor, the lower the maximum humidity set 
point can be.

 

Range : 25 to 90 
Increment: 5 

Default value: 80

 

Summary of Contents for HRO20

Page 1: ...Electrical connection 0 8 mm 2 18 AWG minimum Operating condition 0 C to 40 C 32 F to 104 F 0 95 RH Storage condition 10 C to 50 C 14 F to 122 F 0 95 RH temperature compensation reset feature Automati...

Page 2: ...rom Neptronic humidifier external humidity sensor 0 10 Vdc 2 10 Vdc or high limit 0 10 Vdc 2 10 Vdc AI1 13 Window temperature sensor or outside temperature sensor input AI2 14 Humidify analog output A...

Page 3: ...0 1 C 0 2 F factory calibrated 3 RH Minimum set point Display shows adjust minimum user setpnt and the minimum humidity set point Please select the desired minimum humidity set point The minimum value...

Page 4: ...RH Increment 0 5 RH Default value 5 0 RH 12 RH Control dead band Display shows control dead band and its value Humidify dehumidify symbol are also displayed since this value applies to both Please sel...

Page 5: ...s slightly different than the room typical humidity Range 10 to 90 RH max offset 5 Increment 0 1 RH 0 0 RH no humidity sensor 19 RH Adjust high limit set point If HIL 0 or HIL 2 has been selected at s...

Page 6: ...t s display and adjustment 1 To display the set point s press two times on or 2 If Contol Mode was set to Humidify only or Dehumidify only 2 1 Humidify or Dehumidify set point will be displayed during...

Page 7: ...RH COM Typical Wiring with SK300 BACnet Humidifier Control terminal block wiring Low voltage control terminal block High voltage power terminal block Pressure differential switch High limit humidista...

Page 8: ...T P D SWITCH OTHER INTERLOCK 16 14 15 13 12 HRO20 humidistat Typical Wiring with SKR Humidifier On Off Push button Drain Push button Drain LED Yellow Fan LED Green Access panel Alarm LED Red Power LED...

Reviews: