EFCB Series Controller
Page | 11
ID
7
Name
Description
Writable
Property
EF
CB
12
-G
Rx
EF
CB
1x
EF
CB
1x
-O
E1
EF
CB
1x
Q1
EF
CB
1x
Q1-
O
E
1
EF
CB
1x
Q2
EF
CB
1x
Q2-
O
E
1
EF
CB
1x
Q3
EF
CB
1x
Q4
EF
CB
1x
Q4-
O
E
1
Notes
BV.21
KeyPadArrowLock
37
Keypad arrows lock
Present Value
x x x x x x
x x
x x
0= Off
1= On
BV.22
ContactOutput1
38
Digital output 1 status
Present Value
x x x x
x x
x x
0= Open
1= Close
BV.23
ContactOutput2
39
Digital output 2 status
Present Value
x
x
x x
x x
0= Open
1= Close
BV.24
ContactOutput3
40
Digital output 3 status
Present Value
x x
x
x
0= Open
1= Close
BV.25
ContactOutput4
41
Digital output 4 status
Present Value
x x
x
0= Open
1= Close
BV.26
FanContactLow
Low speed fan contact status
x x x x x x
x x
x x
0= Open
1= Close
BV.27
FanContactMed
Medium speed fan contact status
x x x x x x
x x
x x
0= Open
1= Close
BV.28
FanContactHigh
High speed fan contact status
x x x x x x
x x
x x
0= Open
1= Close
BV.29
OnOffOutput1
42
TO1 output status
Present Value
x x x x x
x x
x x
0= Off
1= On
BV.30
OnOffOutput2
43
TO2 output status
Present Value
x x x x x
x x
x x
0= Off
1= On
BV.31
OnOffOutput3
44
TO3 output status
Present Value
x x x x x
x x
x x
0= Off
1= On
BV.33
DigitalInput1Mode
Flow switch normally open or close
Present Value
x x x x x x
x x
x x
0= Norm.Open
1= Norm.Close
BV.34
DigitalInput2Mode
Dirty filter normally open or close
Present Value
x x x x x x
x x
x x
0= Norm.Open
1= Norm.Close
BV.36
DirtyFilter
Dirty filter status
x x x x x x
x x
x x
0= No
1= Yes
BV.37
FlowSwitch
Flow switch status
x x x x x x
x x
x x
0= No
1= Yes
BV.38
CondensationAlarm
Condensation alarm status
Present Value
x x x x x x
x x
x x
0= No
1= Yes
37
If set “On”, all functionality of these buttons will not be available.
38
Writable if MSV.50 is set OFF. Off means no internal process affected to this output.
39
Writable if MSV.51 is set OFF. Off means no internal process affected to this output.
40
Writable if MSV.52 is set OFF. Off means no internal process affected to this output.
41
Writable if MSV.53 is set OFF. Off means no internal process affected to this output.
42
Writable if MSV.18 is set OFF. Off means no internal process affected to this output.
43
Writable if MSV.19 is set OFF. Off means no internal process affected to this output.
44
Writable if MSV.20 is set OFF. Off means no internal process affected to this output.