background image

 

 Page 22 

Indoor Unit 

Installation

Step 4: Prepare refrigerant piping

The refrigerant piping is inside an insulating 
sleeve attached to the back of the unit. You 
must prepare the piping before passing it 
through the hole in the wall. 

1.  Based on the position of the wall hole relative 

to the mounting plate, choose the side from 
which the piping will exit the unit. 

2.  If the wall hole is behind the unit, keep the 

knock-out panel in place. If the wall hole is to 
the side of the indoor unit, remove the plastic 
knock-out panel from that side of the unit. 

3.

 

If existing connective piping is already 

embedded in the wall, proceed directly to 

the 

Connect Drain Hose

 step. If there is no  

embedded piping, connect the indoor unit’s 

refrigerant piping to the connective piping 

that will join the indoor and outdoor units. 

Refer to the 

Refrigerant Piping Connection

 

 

section of this manual for detailed instructions.

NOTE ON PIPING ANGLE

Refrigerant piping can exit the indoor unit from 

four different angles:Left-hand side,Right-hand 
side, Left rear, Right rear. 

  

Knock-out Panel

 CAUTION

Be extremely careful not to dent or damage 
the piping while bending them away from
the unit. Any dents in the piping will affect 
the unit’s performance. 

Step 5:

 

Connect drain hose

By default, the drain hose is attached to the left-

hand side of unit (when you’re facing the back 

of the unit). However, it can also be attached to 

the right-hand side. To ensure proper drainage, 
attach the drain hose on the same side that your 
refrigerant piping exits the unit. 

 

 

Wrap the connection point firmly with Teflon
tape to ensure a good seal and to prevent leaks. 

 

Remove the air filter and pour a small amount 

of water into the drain pan to make sure that 

water flows from the unit smoothly.

 NOTE ON DRAIN HOSE
 PLACEMENT 

Make sure to arrange the drain hose 

according to the following figures. 

.

PLUG THE UNUSED DRAIN HOLE

To prevent unwanted leaks 
you must plug the unused 
drain hole with the rubber 
plug provided. 

CORRECT 

Make sure there are no kinks
or dent in drain hose to ensure 
proper drainage.   

NOT CORRECT

Kinks in the drain hose 

will create water traps.

NOT CORRECT

Do not place the end of the 
drain hose in water or in 
containers that collect water. 
This will prevent proper 
drainage.     

NOT CORRECT

Kinks in the drain hose 

will create water traps.

Summary of Contents for NS-09EHBIw1

Page 1: ...сь уважно з цим Посібником до моменту встановлення або експлуатації кондиціонера Обов язково зберігайте його для довідок у майбутньому Інструкція з експлуатації та встановлення NS NU 09EHBI NS NU 12EHBI NS NU 18EHBI NS NU 24EHBI ...

Page 2: ...ки 5 Технічні характеристики і функції приладу 7 Посібник з експлуатації без дистанційного управління 12 Догляд і обслуговування 13 Усунення недоліків у роботі 15 Утилізація 17 Підготовка до встановлення 3 Інструкція з експлуатації ...

Page 3: ...истовуйте зазначені Його неправильне підключення може спричинити пошкодження електричних компонентів агрегату підключіть з єднувальний кабель гат від джерела живлення Належним чином Перш ніж виконувати будь які електричні роботи відключить агре УВАГА 1 ПІДГОТОВКА ДО ВСТАНОВЛЕННЯ ує на ймовірність отримання травм або загибелі людей аз Цей символ вк УВАГА ювання з холодоагентами згідно з визнаною в ...

Page 4: ...д пристроїв із Агрегат слід зберігати у приміщенні де немає постійно діючих д рекомендовані виробником зморожування або очищення крім тих які були Не використовуйте засоби призначені для прискорення процесу ро теплової енергії або виникнення пожежі Застосування кабелів із непідходящими параметрами може спричинити появу витоку струму виділення аномальної кількості забезпечує відповідну термічну сті...

Page 5: ...ні роботи та технічне обслуговування цього приладу повинні проводитись спеціалістом авторизованого сервісного центру Ремонт проведений неналежним чином може викликати серйозні травми або пошкодження виробу ЗАСТЕРЕЖЕННЯ ЩОДО ВИКОРИСТАННЯ ВИРОБУ У разі виникнення аномальної ситуації як наприклад запаху горілого негайно вимкніть прилад і витягніть вилку із розетки Зверніться до представника авторизов...

Page 6: ...струмом Для чищення кондиціонера не використовуйте надмірний обсяг води Для чищення кондиціонера не використовуйте горючі миючі засоби Горючі миючі засоби можуть призвести до пожежі або деформації ПОПЕРЕДЖЕННЯ Якщо кондиціонер використовується разом з пальниками або іншими нагрівальними приладами ретельно провітріть приміщення щоб уникнути дефіциту кисню Вимкніть і від єднайте живлення кондиціонер...

Page 7: ...7 Технічні характеристики і функції приладу Частини приладу ...

Page 8: ...я 0 C 43 C 32 F 122 F 15 C 30 C 5 F 75 F 0 C 50 C 32 F 126 F 15 C 50 C 5 F 122 F Для пристроїв з встановленим додатковим низькотемпературним обладнанням Моделі виробів з фіксованою частотою роботи компресора Режим COOL Режим HEAT Режим DRY Температура повітря у приміщенні 17 32 C 62 90 F 0 С 30 C 32 86 F 10 32 C 50 90 F Температура повітря зовні приміщення 18 43 C 64 109 F 7 24 C 19 75 F 11 43 C 5...

Page 9: ...L AUTO COOL або DRY кондиціонер буде продовжувати працювати на дуже малій потужності щоб висушити конденсовану воду і запобігти росту цвілі Виявлення витоку охолоджуючого агенту деякі прилади У разі виявлення витоку охолоджуючого агенту на внутрішньому блоці буде автоматично відображено EC Робота у безшумному режимі деякі прилади Натисканням кнопки LED на пульті дистанційного керування можна вимкн...

Page 10: ...ів для всмоктування або викидання повітря на приладі Високошвидкісний вентилятор всередині блоку може травмувати вас Горизонтальний напрямок повітряного потоку повинен встановлюватись вручну Візьміться за важіль відбивача див Рис 2 3 і вручну налаштуйте у потрібному напрямку На деяких приладах горизонтальний кут повітряного потоку може бути встановлений за допомогою пульта дистанційного керування ...

Page 11: ...температуру повітря у кімнаті на 1 C 2 F через 1 годину а також додатково на 1 C 2 F ще через одну годину В режимі HEAT прилад знижує налаштовану температуру повітря у кімнаті на 1 C 2 F через 1 годину а також буде зменшуватись додатково на 1 C 2 F ще через годину Нова температура буде підтримуватись протягом 7 годин потім прилад вимкнеться автоматично Примітка Функція SLEEP не працює у режимі FAN...

Page 12: ...РЕЖИМІ Прилад повинен бути вимкнений до початку роботи у ручному режимі 1 Знайдіть кнопку ручного управління на правій бічній панелі пристрою 2 Натисніть кнопку MANUAL CONTROL один раз для активації режиму FORCED AUTO 3 Натисніть кнопку MANUAL CONTROL знову для активації режиму FORCED COOLING 4 Натисніть кнопку MANUAL CONTROL в третій раз щоб вимкнути прилад ПЕРІОДИЧНЕ СЕРВІСНЕ ОБСЛУГОВУВАННЯ Для ...

Page 13: ...ластикової поверхні Не використовуйте воду з температурою вище 40 C 104 F для очищення передньої панелі Це може викликати деформування або знебарвлення панелі ОЧИСТКА ПОВІТРЯНОГО ФІЛЬТРА Забитий брудом кондиціонер може зменшити ефективність охолодження а також це може бути шкідливо для вашого здоров я Очищення фільтру потрібно проводити один раз на два тижні 1 Підніміть передню панель внутрішнього...

Page 14: ... екран повернеться до попереднього стану Щоб скасувати нагадування 4 рази натисніть кнопку LED на пульті дистанційного управління або 3 рази натисніть кнопку ручного управління Якщо ви не скасували нагадування індикатор CL буде блимати знову коли ви перезапускаєте прилад Сигналізатор заміни повітряного фільтра Після 2 880 годин роботи на екрані дисплея на внутрішньому блоці блимає nF Це нагадуванн...

Page 15: ... розпилення білого кольору Коли пристрій запускається в режимі HEAT після розморожування розпилення білого кольору може виділятися внаслідок вологи що утворюється на теплообміннику в процесі розморожування Можлива причина Коли жалюзі змінюють налаштування може виникати шипіння Після запуску приладу в режимі HEAT може виникати скрипучий звук внаслідок розширення і стиснення деталей із пластмас Низь...

Page 16: ...редставника або в найближчий авторизований сервісний центр Надайте їм докладний опис несправності приладу а також номер його моделі У разі виникнення несправності перевірте наступні пункти перед зверненням за ремонтом Проблема Можлива причина Вирішення Низька ефективність охолодження Налаштування температури може бути вище кімнатної температури середовища Зниження налаштувань температури Забруднен...

Page 17: ... організації для перевірки на наявність витоків холодоагенту в місцях підключення Лампи індикатора продовжують блимати Прилад може припинити роботу або продовжувати працювати безпечно Якщо лампи індикатора продовжують блимати або з являється помилка коду індикації почекайте близько 10 хвилин Проблема може вирішитись сама по собі Якщо ні вимкніть живлення а потім знову увімкніть Увімкніть прилад Як...

Page 18: ...тажу ВАЖЛИВА ПРИМІТКА Ознайомтесь уважно з цим Посібником до моменту встановлення або експлуатації кондиціонера Обов язково зберігайте його для довідок у майбутньому NS NU 24EHBI NS NU 18EHBI NS NU 12EHBI NS NU 09EHBI ...

Page 19: ...31 Встановлення зовнішнього блоку 32 1 Вибір місця установки 32 2 Встановлення дренажного коліна 33 3 Закріплення зовнішнього блоку 34 4 Під єднання сигнального кабелю і кабелю живлення 35 З єднання трубопроводу з холодоагентом 37 А Примітка щодо довжини трубопроводу 37 В Інструкції для під єднання трубопровід з холодоагентом 37 1 Обрізання труб 37 2 Видалення задирок 38 3 Розширення кінців труб 3...

Page 20: ...лення може призвести до протікання води ураження електричним струмом і пожежі або виходу приладу з ладу Монтажна пластина Затискач Кріпильний гвинт монтажної пластини Пульт дистанційного керування Кріпильний гвинт утримувача пульта дистанційного керування ST2 9 х 10 Утримувач пульта дистанційного керування Суха батарейка AAA LR0 Ущільнювач Дренажне з єднання Опція тільки для охолоджуючих і нагріва...

Page 21: ...21 Стисла інформація про встановлення приладу Вибір місця для встановлення стор 11 Визначення положення отвору у стіні стор 12 Прикріплення монтажної пластини стор 12 Свердління отвору у стіні стор 12 ...

Page 22: ...22 Монтаж внутрішнього блоку стор 18 Обернення трубопроводу і кабелів стор 18 З єднання трубопроводу стор 25 Під єднання кабелю стор 17 Підготовка дренажного шлангу стор 14 ...

Page 23: ...го приладу може дещо відрізнятись Фактична форма має переважне значення Мережевий кабель у деяких приладах Дренажний шланг Сигнальний кабель Трубопровід холодоагенту Пульт дистанційного керування у деяких приладах Держатель пульту Мережевий кабель зовнішнього блоку у деяких приладах Рис 3 1 Жалюзі Передня панель Настінна монтажна пластина ...

Page 24: ...ні стандарти які допоможуть вам вибрати підходяще місце для блоку Примітка для отвору у стіні Правильне місце встановлення відповідає таким стандартам У випадку якщо немає фіксованого трубопроводу з холодоагентом Вибираючи місце встановлення враховуйте що потрібно залишити достатньо місця для отвору у стіні див свердління отвору в стіні для сполучення труб для сигнального кабелю і трубопроводу хол...

Page 25: ...ормації про розміри монтажної пластини 2 Щоб просвердлити отвір у стіні використовуйте порожисте свердло 65мм 2 5 дюйма Переконайтеся що отвір просвердлений під невеликим кутом вниз таким чином щоб кінець отвору назовні був нижчим ніж у кінець у приміщенні приблизно на 5 мм 7 мм 0 2 0 275 дюймів Це забезпечить належний дренаж води див Рис 4 2 3 Просвердліть отвори для кріпильних гвинтів в місцях я...

Page 26: ...ластин з наступними розмірами Ширина монтажної пластини Висота монтажної пластини Ширина внутрішнього блоку по відношенню до пластини Висота внутрішнього блоку по відношенню до пластини Рекомендоване розташування отворів у стіні як ліворуч так і праворуч від монтажної пластини Відносні відстані між отворами для гвинтів Правильне положення монтажної пластини Стіна Внутрішній бік Зовнішній бік Рис 4...

Page 27: ...і протікань цього Посібника Крок 5 Після перевірки протікань оберніть місце з єднання ізоляційною стрічкою Будьте вкрай обережні щоб не пошкодити або пом яти трубопровід при його згинанні від приладу Будь які вм ятини в трубопроводі будуть впливати на продуктивність роботи приладу Крок 6 Зніміть кронштейн або клин який підпирає ізоляційною стрічкою Крок 7 Прикладаючи рівномірний тиск натисніть на ...

Page 28: ...я перевірки протікання газу і перевірки на наявність вм ятин ЗАКУПОРІТЬ НЕВИКОРИСТОВУВАНИЙ ДРЕНАЖНИЙ ОТВІР Для запобігання небажаних витоків необхідно закупорити невикористаний дренажний отвір гумовою втулкою із комплекту Крок 5 Під єднання дренажного шлангу За замовчуванням дренажний шланг кріпиться до лівої сторони блоку коли ви обличчям до спинки приладу Однак він також може бути прикріплений д...

Page 29: ...ркування клієнту і відмовитесь встановлювати прилад до моменту належного вирішення питання безпеки 10 Не дозволяйте проводці зачіпати або упиратись у трубки холодоагенту компресора або рухомих частин всередині блоку 11 Якщо пристрій має допоміжний електричний нагрівач він повинен бути встановлений принаймні 1 метр 40 дюймів від будь яких горючих матеріалів 4 Напруга живлення повинна бути у межах 9...

Page 30: ...івої сторони 6 Протягніть сигнальний дріт через цю щілину із задньої частини приладу у передню ВСЯ ПРОВОДКА ПОВИННА БУТИ ВИКОНАНА СТРОГО У ВІДПОВІДНОСТІ ЗІ СХЕМОЮ ЯКА ЗНАХОДИТЬСЯ ВСЕРЕДИНІ КРИШКИ ПРОВОДКИ ВНУТРІШНЬОГО БЛОКУ Крок 6 Під єднайте сигнальний кабель Сигнальний кабель забезпечує зв язок між внутрішнім і зовнішнім блоками Ви повинні спочатку вибрати правильний розмір кабелю перед його під...

Page 31: ...оку Якщо ви встановили на зовнішньому блоці нову сполучну трубу виконайте такі дії 1 Якщо ви вже проклали трубу з холодоагентом через отвір в стіні перейдіть до кроку 4 2 В іншому випадку двічі перевірте герметичність кінців труб з холодоагентом для запобігання забрудненню або попадання чужорідних матеріалів 3 Повільно просуньте згорток з труб холодоагенту дренажного шлангу і сигнального кабелю че...

Page 32: ...овленні Рис 4 1 Поруч з будь якою перешкодою що може блокувати циркуляцію повітря Добра циркуляція повітря і вентиляція Поблизу вулиці загального користування місць скупчення людей або там де шум від блоку буде заважати іншим людям Міцне і тверде місце може підтримувати пристрій і не вібрує Поруч з тваринами або рослинами які будуть постраждали від гарячого повітря Шум від блоку не заважає іншим л...

Page 33: ...у вітру За необхідності облаштуйте бар єр спереду приладу щоб захистити його від надмірно сильного вітру Див рис 4 2 і рис 4 3 нижче В УМОВАХ ХОЛОДНОГО КЛІМАТУ У умовах холодного клімату встановіть дренажний шланг якомога вертикальніше щоб забезпечити швидке відведення води Якщо вода стікає занадто повільно вона може замерзнути в шлангу і затопити блок Якщо прилад часто знаходиться під сильним дощ...

Page 34: ...2x363 33 25 x27 63 x14 29 540 21 26 350 13 8 900x860x315 35 4 x33 85 x12 4 590 23 2 333 13 1 945x810x395 37 2 x31 9 x15 55 640 25 2 405 15 95 946x810x420 37 21 x31 9 x16 53 673 26 5 403 15 87 946x810x410 37 21 x31 9 x16 14 673 26 5 403 15 87 Якщо ви будете встановлювати прилад на землі або на бетонній монтажній платформі виконайте такі дії 1 Відмітьте місця для чотирьох розпірних болтів відповідно...

Page 35: ...равильному заземленні кондиціонера 9 Кожен провід повинен бути надійно підключений Ненадійна проводка може призвести до перегріву сполучної коробки у результаті чого виріб може вийти з ладу і може виникнути пожежа 10 Не дозволяйте проводці зачіпати або упиратись у трубки холодоагенту компресора або рухомих частин всередині блоку 11 Якщо пристрій має допоміжний електричний нагрівач він повинен бути...

Page 36: ...ь його вбік 4 Підберіть кольори дротів до міток на клемній колодці підключіть U наконечник і закрутіть міцно кожен дріт на відповідній клемі 5 Після перевірки безпеки кожного з єднання оберніть дріт навколо щоб запобігти попаданню дощової води у клемну коробку 6 За допомогою кабельного затискача прикріпіть кабель до пристрою Щільно загвинтити кабельний затискач Інші регіони Номінальний струм прила...

Page 37: ...ний кондиціонер з однією спліт системою 15000 10 33 футів 15000 і 24000 20 66 футів 24 000 і 36000 25 82 футів 36000 і 60000 3 25 метрів 5 30 метрів 7 50 метрів 7 65 метрів 30 98 5 футів Інструкції для під єднання трубопровід з холодоагентом 2 За допомогою труборізу відрізати трубу трохи довше ніж виміряна відстань Крок 1 Обрізання труб Під час підготовки труб з холодоагентом потрібно бути дуже об...

Page 38: ...огою розширювача або інструменту для видалення задирок видаліть задирки з обрізаної частини труби Крок 3 Розширення кінців труб ВИСТУП ТРУБОРОВОДУ ЗА МЕЖІ ФОРМИ ДЛЯ РОЗШИРЕННЯ Правильне розширення є істотним для отримання герметичного ущільнення Зовнішній діаметр труби мм А мм Мін Макс Ø 6 35 Ø 0 25 0 7 0 0275 1 3 0 05 Ø 9 52 Ø 0 375 1 0 0 04 1 6 0 063 Ø 12 7 Ø 0 5 1 0 0 04 1 8 0 07 Ø 16 Ø 0 63 2 ...

Page 39: ...чи штуцер на трубопроводі за допомогою гайкового ключа затягніть гайку відповідно до значень крутного моменту наведених нижче у таблиці Вимоги до крутного моменту Злегка послабити гайку а потім затягнути знову МІНІМАЛЬНИЙ РАДІУС ЗГИНАННЯ Під час згинання з єднувальної труби холодоагенту мінімальний радіус згинання складає 10 см Див Рис 5 6 ВИМОГИ ДО КРУТНОГО МОМЕНТУ Зовнішній діаметр труби мм Моме...

Page 40: ... захисні ковпачки з кінців арматури 3 Зіставте розширений кінець труби з кожним клапаном і затягніть міцно гайку вручну 4 За допомогою гайкового ключа міцно стисніть корпус клапана Не беріться за гайку яка герметизує сервісний клапан Рис 5 10 5 Міцно стискаючи корпус клапана за допомогою гайкового ключа затягніть гайку відповідно до правильних значень моменту затяжки 6 Злегка послабте гайку а поті...

Page 41: ... повинне проводитись при першому встановленні і після переміщення блоку ДО ПОЧАТКУ ОЧИЩЕННЯ Переконайтеся що обидва трубопроводи високого тиску і низького тиску між внутрішнім і зовнішнім блоками правильно під єднанні відповідно до розділу Під єднання трубопроводу з холодоагентом даного посібника Переконайтеся що всі дроти правильно підключені 1 Підключіть заправний шланг манометра до сервісного п...

Page 42: ...ми а потім закрийте клапан через 5 секунд 10 Спостерігайте за манометром протягом однієї хвилини щоб переконатися що немає ніяких змін тиску Манометр повинен показувати тиск трохи вищий ніж атмосферний Примітка про додавання холодоагенту Деякі системи вимагають додаткової зарядки в залежності від довжини труби Стандартна довжина труби варіюється залежно від місцевого законодавства Наприклад у Півн...

Page 43: ...ристовуючи м яку щітку нанесіть мильну воду або рідкий миючий засіб на всі точки з єднання труб на внутрішньому і зовнішньому блоках Наявність бульбашок вказує на витік Примітка Ця вимога може встановлюватись у деяких місцевостях в США Метод детектора витоку При використанні детектора витоку зверніться до Посібника з експлуатації приладу для отримання інструкцій щодо використання ПІД ЧАС ПРОБНОЇ Е...

Page 44: ... проводитись тільки після виконання наступних кроків Перевірка безпеки електричної системи Переконайтеся що електрична система пристрою є безпечною і працює належним чином Перевірка витоку газу Перевірте всі вальцовачні з єднання і переконайтеся що система не протікає Переконайтеся що газовий і рідинний клапани високого і низького тиску повністю відкриті Вказівки для пробної експлуатації Пробна ек...

Page 45: ...рніть блок до нормальної робочої температури б Використовуючи ізоляційну стрічку оберніть точки з єднань труб холодоагенту внутрішнього блоку що залишились не оберненими протягом встановлення внутрішнього блоку ЯКЩО КІМНАТНА ТЕМПЕРАТУРА НИЖЧЕ 17 С 63 F Ви не можете використовувати пульт дистанційного керування щоб увімкнути функцію COOL коли кімнатна температура нижче 17 С У цьому випадку ви может...

Page 46: ...тановою Кабінету Міністрів України від 24 травня 2017р 360 Декларації про відповідність можна знайти на сайті www optіm ua у розділі Підтримка Адреса потужностей виробництва ГД МІДЕЯ Індустріал Сіті Бейжао Шунде 528 311 Фошань Гуандонг Китайська Народна Республіка Уповноважений Представник в Україні ТОВ ТОРГОВА КОМПАНІЯ ОПТІМ Україна 03134 м Київ вул Пшенична 9 тел 044 406 40 46 факс 044 406 40 45...

Page 47: ... before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer information from the Owner s Manual Product Fiche in the packaging of the outdoor unit European Union products only ...

Page 48: ... Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 12 Troubleshooting 14 1 Indoor unit display 07 2 Operating temperature 09 3 Other features 10 4 Setting angle of airflow 11 5 Manual operation without Remote 11 ...

Page 49: ...nt indoor unit 25 Outdoor Unit Installation 26 1 Select installation location 26 2 Install drain joint 27 3 Anchor outdoor unit 27 4 Connect signal and power cables 29 Refrigerant Piping Connection 30 A Note on Pipe Length 30 B Connection Instructions Refrigerant Piping 30 1 Cut pipe 30 2 Remove burrs 31 3 Flare pipe ends 31 4 Connect pipes 31 Air Evacuation 33 1 Evacuation Instructions 33 2 Note ...

Page 50: ...ises like a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit This may cause fire or combu...

Page 51: ...share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which has at least 3mm clearances in all poles and have a leakage current that may exceed 10mA the residual current device RCD having a rated residual operating current not exceeding 30mA and disconnection mu...

Page 52: ... install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit i...

Page 53: ...chanical connectors are reused indoors sealing parts shall be renewed When flared joints are reused indoors the flare part shall be re fabricated IEC Standard Requirements European Disposal Guidelines This appliance contains refrigerant and other potentially hazardous materials When disposing of this appliance the law requires special collection and treatment Do not dispose of this product as hous...

Page 54: ... when TIMER ON is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned off when defrosting cooling heating units when anti cold air feature is turned on when unit is self cleaning when 8 C heating feature is turned on Displays temperature operation feature and Error codes Illustrations in ...

Page 55: ...22 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems To further optimize the performance of your unit do the following Keep doors and windows closed Limit energy usage by using TIMER ON and TIMER OFF functions Do not block air inlets or outlets Regular...

Page 56: ... settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep When in COOL mode the unit will increase the temperature by 1 C 2 F after 1 hour and will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by...

Page 57: ...gers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig B Fig A Setting Angle of Air Flow Setting horizontal angle of air flow To operate your unit manually 1 Open the front panel of the indoor unit 2 Locate the MANUAL CONTROL button on the right hand side of the unit 3 Press the MANUAL CONTROL button one time to activate FORCED AUTO mode 4 P...

Page 58: ...o be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3 Now pull the filter out 4 If your filter has a small air freshening filter unclip it from the larger filter Clean this air freshening filter with a hand held vacuum 5 Clean the large air filter with ...

Page 59: ...e If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the power Remove batteries from remote control Maintenance Pre Season Inspection After long periods of non use or before periods of frequent use do the following Check for damaged wires Clean all filter...

Page 60: ...s Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the indoor unit and outdoor unit make noises Low hissing sound during operation This is norm...

Page 61: ...t customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solution Poor Cooling Performance Temperature setting may be higher than ambient room temperature Lower the temperature setting The hea...

Page 62: ...Poor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re seal if necessary and top off refrigerant Indicator lamps continue flashing The unit may stop operation or continue to run safely If th...

Page 63: ...ape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote controller holder optional Remote controller holder optional Drain joint for cooling heating models Seal for cooling heating models Mounting plate Manual Parts you must purchase separately Consult the dea...

Page 64: ... Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in the US Connect Piping Prepare Drain Hose Connect Wiring not applicable for some locations in the US 4 5 6 7 8 9 ...

Page 65: ...e requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller Drainage Pipe Louver Remote controller Holder Some Units Functional Filter On Back of Main Filter Some Units Front Panel Outdoor Unit Power Cable Some Units 1 2 3 4 5 6 7 8 9 10 11 1 2 1 2 3 4 6 7 8 ...

Page 66: ...direct sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective piping step for the signal cable and refrigerant piping that connect the indoor and outdoor units The default position for all piping is the right side of the indoor unit while facing the unit However the...

Page 67: ...re to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outline 722mm 28 45in 49mm 1 95in 192mm 7 55in 232mm 9 15in 426mm 16 8in 128mm 5 05in 43mm 1 7in 297mm 11 7in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Left rear wall hole 65mm 2 5in Right re...

Page 68: ...k out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the unit s performance Step 5 Connect drain hose By default the drain hose is attached to the left hand side of unit when you re facing the back of the unit However it can also be attached to the right hand side To ensure proper drainage attach the dra...

Page 69: ...rmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire Do not let wires touch or rest against refrigerant tubing the compressor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To avoid getting an electric shock never touch the el...

Page 70: ...l on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can lead to fire or water damage DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES While bundling these items together do not intertwine or cross the signal cable with any other wiring 2 Using adhesive vinyl ...

Page 71: ... pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate 7 Again check that the unit is firmly mounted by applying slight pressure to the left and the right hand sides of the unit If refrigerant piping is alrea...

Page 72: ... wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or snow Build a shelter above the unit to protect it from the rain or snow Be careful not to obstruct air flow around the unit If the unit is frequently exposed to salty air seaside Use outdoor unit that ...

Page 73: ...ubber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode Seal Drain joint A B Base pan hole of outdoor unit Seal IN COLD CLIMATES In cold climates make sure that the drain hose is as vertical as poss...

Page 74: ...ce a nut on the end of each expansion bolt 4 Hammer expansion bolts into the pre drilled holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRILLING INTO CONCRETE EYE PROTECTION IS RECOMMENDED AT ALL TIMES CAUTION Make sure that the wall is made of solid bri...

Page 75: ...clamp down tightly 7 Insulate unused wires with PVC electrical tape Arrange them so that they do not touch any electrical or metal parts 8 Replace the wire cover on the side of the unit and screw it in place 1 Remove the wire cover from the unit by loosening the 3 screws 2 Dismount caps on the conduit panel 3 Temperarily mount the conduit tubes not included on the conduit panel 4 Properly connect ...

Page 76: ...er than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrigeration cycle This can cause explosion and injury 2 Using a pipe cutter cut the pipe a little longer than the measured distance 3 Make sure that the pipe is cut at a perfect 90 angle Oblique Rough Warped 90 DO NOT DEFORM PIPE ...

Page 77: ...alling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve an airtight seal 1 After removing burrs from cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends ...

Page 78: ... 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm Ø 9 52 Ø 0 375 Ø 12 7 Ø 0 5 Ø 16 Ø 0 63 Ø 19 Ø 0 75 1 Unscrew the cover from the packed valve on the side of the outdoor unit 2 Remove protective caps from ends of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Us...

Page 79: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no change in system pressure 8 If there is a change in system pressure refer to Gas Leak Check section for information on how to check for leaks If there is no change in system pressur...

Page 80: ...u h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Liquid Side Ø 6 35 ø 0 25 R32 Pipe length standard length x 12g m Pipe length standard length x 0 13oZ ft R290 R290 Pipe length standard length x 10g m Pipe length standard length x 0 10oZ ft Liquid Side Ø...

Page 81: ... Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using leak detector refer to the device s operation manual for proper usage instructions AFTER PERFORMING GAS LEAK CHECKS After confirming that the all pipe connection points DO NOT leak replace the valve...

Page 82: ...the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe connection points do not have leaks Refer to Gas Leak Check section for instructions 5 After the Test Run is successfully completed and you confirm that all checks points in List of Checks to Perform...

Page 83: ...ly authority for system impedance information This appliance MST2ABF 30CR QB9W can be connected only to a supply with system impedance no more than 0 085Ω In case necessary please consult your supply authority for system impedance information This appliance MSTABD 18CR QB8 can be connected only to a supply with system impedance no more than 0 188Ω In case necessary please consult your supply autho...

Page 84: ... specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the latest version Test Run ...

Page 85: ...IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference SAFETY MANUAL CAUTION Risk of fire ...

Page 86: ... circuit should hold a current valid certificate from an industry accredited assessment authority which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification 3 Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable ref...

Page 87: ... heights are given below 0 0 m for portable and floor mounted 1 0m for window mounted 1 8m for wall mounted 2 2m for ceiling mounted If the minimum installed height given by the manufacturer is higher than the reference installed height then in addition Amin and mmax for the reference installed height have to be given by the manufacturer An appliance may have multiple reference installed heights I...

Page 88: ...2 146 328 584 912 1541 30 53 118 210 328 555 9 16 36 65 101 171 6 11 24 43 68 115 196 60 40 Min Room Area m 2 Minimum Room Area m 2 Refrigerant Type Installation Height H0 m The maximun charge in a room and the required minumum floor area to install an applicance please refer to the Owner s Manual Installation Manual of the unit For specific information on the type of gas and the amount please ref...

Page 89: ...undertaken with appropriate tools only In case of uncertainty please consult the manufacturer of the tools for use with flammable refrigerants The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with flammable refrige...

Page 90: ...tely but it is necessary to continue operation and adequate temporary solution shall be used This shall be reported to the owner of the equipment so all parties are advised Initial safety checks shall include that capacitors are discharged this shall be done in a safe manner to avoid possibility of sparking that there no live electrical components and wiring are exposed while charging recovering o...

Page 91: ...eed re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas 25 maximum is confirmed Leak detection fl...

Page 92: ...g shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved then venting to atmosphere and finally pulling down to a vacuum This process shall be repeated until no refrigerant is within the system When the final OFN charge is used the system shall be vented down to atmospheric pressure to enable work to take place This operation i...

Page 93: ...associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to...

Page 94: ...ing should only take place on the certainty that the refrigerant will not get blown back into any adjacent buildings and that it will not migrate to a location below ground level The hose is made of material that is compatible for use with HC refrigerants and oil A device is used to raise the hose discharge at least 1 m above ground level and so that the discharge is pointed in an upwards directio...

Page 95: ...r unit Page 10 1 Transport of equipment containing flammable refrigerants Compliance with the transport regulations 2 Marking of equipment using signs Compliance with local regulations 3 Disposal of equipment using flammable refrigerants Compliance with national regulations 4 Storage of equipment appliances The storage of equipment should be in accordance with the manufacturer s instructions 5 Sto...

Page 96: ... without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please check for the latest version SAFETY MANUAL R32 R290 16122200002889 20190303 ...

Reviews: