background image

6

  Figure 5 - Conductivity Probe Installation

1   Drill the enclosure as needed and install liquid-

tight fittings for the wiring.

   

 

NOTE: 

 

The Controller can be ordered 

pre-drilled or with fittings installed, or with 

fittings and wiring installed. Contact Nelsen 

Corporation for details.

2   Mount the enclosure in the desired location on 

the RO system.

3   Bring the wires from the peripheral devices 

into the enclosure and connect them to the 

appropriate terminals. (See Figure 1, Figure 3 and 

Figure 4.)

4   Set the voltage selector switch on the Terminal 

Board to the desired voltage (120VAC or 240VAC) 

(See Figure 4.)

Controller Power Fuse Values

 

.5 HP  .75 HP  1 HP 

2 HP

  120 VAC 

12 A 

20 A 

20A 

N/A

  240 VAC 

6 A  

12 A

7   Connect the conductivity cell to the terminals on 

the CPU Board. (See Figure 3)

8   Provide power to the RO system.
9   Press the System On/Off switch to turn the 

system ON.

10   Select the Program Mode (See Figure 6 and Table 

2). The default is Program 1 which is a general 

purpose setting. Use Program 2 if your system is 

not equipped with a flush valve.

   

 NOTE:

  

The Program Settings can be 

customized to suit the specific needs 

of an OEM and pre-programmed at the 

factory with your settings. Contact Nelsen 

Corporation for details.

11   Make any other changes you want to the 

settings. Press System On/Off to save your 

changes.

12  The controller is now ready for service.

   

 

NOTE:

  If using a single point High Level RO 

water shut off/liquid level control, you need 

to install a Jumper wire on the Terminal strip 

from E24 to E26. Connect the float switch 

wires to terminals E23 and E26. Connection 

E25 is empty...no wire connection.

5   Install the correct power fuse for your voltage/

motor HP. See the table below and Figure 4.

6   Install the conductivity cell in the permeate line. 

(See Figure 5 for conductivity cell installation 

instructions.)

 Installation

Install the Conductivity Probe in the “Run” 

of a Tee or equivalent location. Orient the 

probe so that air can not become trapped in 

the area near the probe.

FL

OW

FLOW

Conductivity 
Probe

Summary of Contents for NRO ROC2

Page 1: ...Nelsen NRO ROC2 System Controller Documentation ...

Page 2: ...n Figure 5 6 Installation Instructions 6 Controller Programming Accessing Hidden Menus Figure 6 7 System Start up w Permeate Flush 7 Controller Programming Program Selections Table 2 8 Controller Programming Menu Navigation Figure 7 9 Controller Programming Parameters Explained Appendix A 10 11 Controller Fault Displays 11 12 Controller Programming Programming Interface Overview 13 Warranty 14 ...

Page 3: ...ay Ratings Feed Solenoid 10A Resistive 5A Inductive Voltage is the same as motor supply voltage Flush Solenoid 10A Resistive 5A Inductive Voltage is the same as motor supply voltage Motor 40A Resistive 240 VAC 1 0 HP 120V 2 0 HP 240V Circuit Protection Main Power Fuse 110V F1 3AG 20 Amp LittleFuse 314 020 P For up to 1 HP motor F1 3AG 4 Amp LittleFuse 312 004 P Motor contactor coil Main Power Fuse...

Page 4: ...2 Figure 1 Simplified Schematic i Figure 1 Simplified Schematic ...

Page 5: ...F Up Arrow Down Arrow Manual Run Manual Flush CPU Board CPU Board Conductivity Probe Connections Display 4 line 20 character Clear concise feedback on the RO s status Alarm Display backlight flashes along with audible beeper to indicate alarm condition ...

Page 6: ...ield White Black Cable to Terminal Board Figure 3 Controller Detail CPU 3 Typical Configuration G T C G T C TDS Probe 2 TDS Probe 1 Conductivity Programing Port used with optional programming interface See Appendix B for explanation of the programming interface Main interface port Connects via ribbon cable to Terminal Board Sel 1 and Sel 2 Jumpers Special purpose jumpers ...

Page 7: ...y external voltage Alternate wiring for single level switch Tank Lo Tank Hi 240 VAC 120 VAC F2 Controller Power Fuse F3 Solenoid Power Fuse F1 Main Power Fuse Inlet Valve Relay Flush Valve Relay Switch LEDs Illuminate when switches close Feed and Flush Solenoid LEDs Illuminate when the relay is energized Pump LED Illuminates when the motor relay is energized Transformer Figure 4 Controller Detail ...

Page 8: ...nd Table 2 The default is Program 1 which is a general purpose setting Use Program 2 if your system is not equipped with a flush valve NOTE The Program Settings can be customized to suit the specific needs of an OEM and pre programmed at the factory with your settings Contact Nelsen Corporation for details 11 Make any other changes you want to the settings Press System On Off to save your changes ...

Page 9: ...em On Off button This will switch to the Hidden Menus as shown above 3 If not already on the RO Presets Program Press the Up or Down Arrows until you reach this screen 4 Once on the RO Presets Program Screen Press Manual to Edit this Screen 5 Press the Up or Down Arrow to change to Program 2 6 Once on Program 2 Press Manual to Exit the screen Manual Run Flush RO Presets Program 1 to change setting...

Page 10: ...terval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5 5 5 5 Low pressure fault shutdown time period to count faults Minutes 10 10 10 10 Low pressure fault shutdown reset after shutdown Minutes 60 60 60 60 Low pressure fault alarm relay output TB 2 ONLY Off On Off Off Off Off Low pressure time out fault Seconds 60 60 60 60 Flush Behavior Extra Maximu...

Page 11: ...Sys Save VALUES uS PPM None LCD Brightness 10 for other menus Manual Edit Sys Save LCD Brightness 10 to change setting Manual Edit Sys Save VALUES 0 15 LCD Contrast 15 for other menus Manual Edit Sys Save LCD Contrast 15 to change setting Manual Edit Sys Save VALUES 0 15 Save Return to RO Display System On Off System On Off Manual Run Flush Save Return to RO Display System On Off Manual Run Flush ...

Page 12: ...ing against a closed suction as the pump spins down Low Inlet Pressure Behaviors Pump start retry interval restart delay after LP fault Seconds 60 When the inlet pressure switch opens the controller deenergizes the motor and the inlet solenoid valve remains open The controller will continue to monitor the inlet pressure switch After the switch is closed for the duration of the Pump start retry int...

Page 13: ...ets the duration of the Idle Flush 0 disabled Timed Manual Run Duration of Manual Run Minutes 5 Timed Manual Flush Duration of Manual Flush Minutes 5 Conductivity Probe Sample Rate Seconds 2 Conductivity Shutdown 0 disabled Minutes 0 Controller Fault Condition Displays Below are examples and explanations of the displays which accompany the fault conditions possible in the ROC 3 Fault conditions al...

Page 14: ...nt If RO Not Working and Display Shows Tank Full or Tank Full Draw Down 1 If using a single point high level float switch the jumper in the wiring instructions must be installed This needs to be checked to make sure it is not loose and or disconnected which would cause a failure and one of the displays above ie Remove jumper and reinstall making sure of a good connection Re check display and opera...

Page 15: ...d tool for making changes to the ROC software The program combines a simulator for testing your changes on the PC and an communications programming interface for loading the software into the controller The Interface can also be used to remotely monitor the RO This screen shows the 4 sets of user configurable values ...

Page 16: ...e 1 To obtain warranty service contact your selling dealer for a Return Material Authorization RMA 2 You will be required to provide a Your name and address b A description of the problem 3 Package the controller carefully for shipment and return it to your freight prepaid Limitation of implied warranties There are no warranties expressed or implied which extend beyond the description contained he...

Reviews: