FlexPAK
4.2.9 Presep
Menu for activating automatic emptying of two pre-separators. This cannot be used together with TVFD.
Presep activates PresepTm to control the TVFD Solenoid Upper Valve (SUV). It uses BinOpnTm to control the
TVFD Solenoid Lower Valve (SLV).
ESC
OK
Presep
1/1
Switch = Off
Switch=Off is the default setting; Presep is deactivated and TFVD is activ-
ated.
To activate Presep, set Switch=On.
4.2.10 MFDPS-Wr
Menu for setting the Main Filter Differential Pressure Sensor Warning (MFDPS-Wr) delay timer. When the Main
Filter pressure sensor monitoring detect High dP across Main Filter, MFDPS-Wr is activated, and the delay
timer has expired, the Main Filter Clogged warning message is activated. See
Section 3.2.2 Warning! Main Filter
.
ESC
OK
MFDPS-Wr
1/1
T
= 00:08m
Ta = 00:00m
T=10:00m Time before MFDPS-Wr is activated. The default is 10 minutes.
Ta=00:00 The elapsed time since High dP across Main Filter was detected.
4.2.11 MFDPS-FC
Menu for setting the Main Filter Differential Pressure Sensor Filter Cleaning (MFDPS-FC) delay timer. When
the Main Filter pressure sensor monitoring detect High dP across Main Filter, MFDPS-FC is activated, and the
delay timer for MFDPS-FC has expired, it activates automatic filter cleaning if DPFClean is activated, see
. If PSIFC is set to ‘On’, the filter cleaning sequence will not be activated.
ESC
OK
MFDPS-FC
1/1
T
= 01:00m
Ta = 00:00m
T=01:00m: Time before MFDPS-FC is activated. The default setting is 1
minute.
Ta=00:00: The elapsed time since High dP across Main Filter was detected.
4.2.12 BLI-Empt
Menu for setting the BLI emptying delay time for the bin level indicator. This function is only available when Li-
Auto is set to ‘On’, see
When the BLI signal disappears, the BLI-Empt delay timer is activated, when the timer elapses, the timer activ-
ates the dust bin emptying sequence with either the AEB - Flap Valve, simple TVFD, Advance TVFD or pre-sep-
arator.
If AEB-TVFD is set to ‘On’, in other words, the AEB-Flap Valve is chosen, the bin emptying sequence is inter-
locked when PSIFC is set to ‘On’. See
.
ESC
OK
BLI-Empt
1/1
T
= 10:00s
Ta = 00:00s
T=10:00m: Time before BLI-Empt is activated. The default is 30 minutes.
Ta=00:00: The elapsed time since the BLI-Wr warning message was activ-
ated.