FlexPAK
4.2.30 FlushCy1
Menu for setting the amount of time for automatic flushing of the duct system by flushing valve 1 (SFV1). If
PSCFlush is deactivated, FlushCy1 is activated by FlushTmr. If PSCFlush is activated and there is no pilot signal.
‘T’ is how long the flushing valve is open.
ESC
OK
FlushCy1
1/1
T
= 10:00s
Ta = 00:00s
T=10:00s: Time flush valve 1 (SFV1) is open. The default setting is 10
seconds.
Ta=00:00: The elapsed time since the flushing cycle started.
4.2.31 VacLoTm
Delay Timer for “Warning! Low Vacuum”, see
Section 3.2.5 Warning Low Vacuum
.
This timer delays showing the message “Warning! Low Vacuum “ when the vacuum is too low in the system. The
timer serves as a filter to remove short-term vacuum variations in the system. When the timer expires, the mes-
sage “Warning! Low Vacuum “ is displayed.
ESC
OK
VacLoTm
1/1
T
= 01:00m
Ta = 00:00m
T = 01: 00m default setting 1 minute delay
Ta = 00: 00m shows the lukewarm delay time
4.2.32 PSIFC
Menu for activating Pilot Signal Interlock Filter Cleaning (PSIFC). Filter cleaning does not take place until the pi-
lot signal has disappeared and DIR_Time has expired.
If AEB-TVFD is set to ‘On’, in other words, AEB-Flap Valve opening is chosen, the bin emptying sequence is also
interlocked when there is a pilot signal to the unit.
ESC
OK
PSIFC
1/1
Switch = Off
4.2.33 PresepTm
Menu for AEB-Flap Valve, simple TVFD and pre-separator opening cycle settings. The values for ‘TL’ and ‘TH’ de-
pend on which function is being used. See
ESC
OK
PresepTm
1/1
TH = 05:00s
TL = 03:00s
Ta = 00:00s
TL= See
.
37