background image

FlexPAK

5.8 Automatic bin emptying function

See the PLC Settings Manual.

5.9 Machining chips and swarf extrac-
tion

See the PLC Settings Manual.

5.10 Pneumatic filter cleaning valve

See the PLC Settings Manual.

5.11 Vacuum setpoint

Performance settings with two typical running modes:

1000 m3/h at -15 kPa, max vacuum 20kPa or 800 m3/h
at -20 kPa, max vacuum 35 kPa. The vacuum setpoint
can be switched between -20kPa and -35kPa by alter-
ing a terminal X2:1 in the control box. The default set-
ting is -20kPa.

See 

Figure 7

 item 4 and the wiring diagram.

5.12 Rotary valve

See the PLC Settings Manual.

5.13 Compressed air installation

WARNING! Risk of personal injury
• Use ear protection and safety goggles.
• The compressed air valve is to be locked in

the closed position during maintenance.

5.13.1 Requirements

NOTE! 
• The specified air consumption of the unit is

limited to the short operation of the cleaning
valve.

• Take measures necessary to avoid water or

humidity in the compressed air when the unit
is installed in cold environments.

• If antifreeze additives are used, use them

continuously. Once added, the removal of the
antifreeze additive may cause the pneumatic
components to malfunction.

For air consumption, quality and maximum and minim-
um pressure, see 

Section 3.3 Technical data

.

As new ducts may contain dirt, particles or debris, the
compressed air pipe is to be blown clean before con-
necting the unit. A compressed air filter, see 

Figure 9

,

item 7, is to be installed to ensure the reliable and safe
operation of the unit. A compressed air valve, that
vents the remaining pressure of the unit, is to be in-
stalled, see 

Figure 9

, item 6.

5.13.2 Installation

NOTE! 
Secure the compressed air line properly.

Connect a compressed air supply to the inlet, see 

Fig-

ure 5

, item 20, and 

Figure 9

, items 6 and 7.

Air pressure hoses are to be fitted together with
electrical cables with straps, alternatively in a com-
mon protective hose. Air pressure hoses are to be
anchored mechanically.

6 Maintenance

Read 

Chapter 3 Description

 before carrying out any

maintenance work.

Maintenance work means that the equipment will
have to be opened and possibly dismantled. This may
constitute a risk and the maintenance personnel need
to know about the risks that may occur when acting
incorrectly.

WARNING! Explosion risk
Stop operation and clean the entire filter thor-
oughly from dust before any grinding, welding
or other hot works are performed on the filter
exterior or inlet.

WARNING! Risk of personal injury
• Always use an approved breathing mask,

goggles and gloves when replacing the dust
sack and other work that involves exposure
to dust.

• The motor, fan and air duct may become very

hot during operation.

• Use ear protection when the unit is in opera-

tion and work is carried out in the vicinity of
the upper section of the dust collector.

• Always disconnect the supply voltage with

the maintenance switch before any service,
whether mechanical or electrical.

• Always lock the maintenance switch in the

off position and, if possible, secure it with a
padlock.

• Always disconnect the compressed air sup-

ply before any service, whether mechanical
or electrical.

• Parts may be very heavy. Always use ad-

equate lifting equipment when handling
parts and consumables.

• Always use adequate safety measures when

performing work in an elevated position.

CAUTION! Risk of equipment damage
During maintenance, it may be necessary to re-
move the acoustic enclosure over the motor
while the motor is in operation. Take care to
prevent objects from falling down into the mo-
tor cooling fan.

21

Summary of Contents for FlexPAK Standard

Page 1: ...Installation and Service Manual Compact dust collectors FlexPAK Standard Models Original installation and service manual EN INSTALLATION AND SERVICE MANUAL 2022 10 28 144838 07...

Page 2: ...FlexPAK Trace back information Workspace Main version a68 Checked in 2022 10 28 Skribenta version 5 5 022...

Page 3: ...2 Outdoor installation 20 5 4 3 Moving the unit 20 5 5 Electrical installation 20 5 6 General requirements 20 5 7 Ground check measurement 20 5 8 Automatic bin emptying function 21 5 9 Machining chips...

Page 4: ...f the start and control unit 25 7 3 Troubleshooting guide 25 8 Spare Parts 27 8 1 Ordering spare parts 27 9 Recycling 27 9 1 Environmental information 27 10 Acronyms and abbreviations 28 11 Appendix A...

Page 5: ...FlexPAK Figures AB Ph Nederman Co SWEDEN Type Art no V Ser no Hz kW 50 A kW V A 60 Hz Year of manufacture hp 1 907mm 35 7 966mm 38 0 2116mm 83 5 1670mm 66 0 EMERGENC Y S T O 2 5...

Page 6: ...FlexPAK 13 12 10 9 7 8 2 1 3 4 6 5 11 3 11 7 8 9 12 13 15 14 18 19 10 17 4 16 15 20 5 6...

Page 7: ...FlexPAK 6 1 2 3 6 7 8 9 16 15 14 13 11 10 12 4 5 7 7...

Page 8: ...FlexPAK EMERGENCY STOP SIEMENS LOGO 12 24RC XXXXXXX XXXXX XXXX ESC OK Stop Set Param Set Prg Name 6 1 5 4 2 3 8 8...

Page 9: ...FlexPAK 2 1 4 5 6 8 7 9 3 9 1 1643 1mm 65 662 1mm 26 2 1771 4 1mm 70 13mm 10 9...

Page 10: ...FlexPAK 11 12 13 14 10...

Page 11: ...FlexPAK 15 A B 16 11...

Page 12: ...FlexPAK A B C 4x 17 8x 18 12...

Page 13: ...FlexPAK A 4x B 19 Min 2 1m 83 20 1 0m 39 4 21 13...

Page 14: ...FlexPAK A B C 22 23 14...

Page 15: ...indicate a potential hazard to the health and safety of personnel and how that hazard may be avoided CAUTION Risk of equipment damage Cautions indicate a potential hazard to the product but not to pe...

Page 16: ...cording to EN 60335 2 69 Weight 439 kg 968 lb 439 kg 968 lb Inlet outlet diameter 150 160 mm 7 87 6 29 150 160 mm 7 87 6 29 Sound level 70 dB A 70 dB A Ambient temperature range 0 40 C 32 104 F 0 40 C...

Page 17: ...15 Outlet silencer after fan see Figure 4 and Fig ure 5 16 Cooling air hose from the frequency converter cabinet see Figure 5 17 Inlet silencer before the fan see Figure 4 18 Pressure sensor see Figu...

Page 18: ...d according to the electrical diagrams that came with the unit Consult your local Nederman represent ative for available accessories The most common accessory is a PS cable which al lows remote start...

Page 19: ...ions Transport velocity It is important to use the correct duct diameter to avoid pressure losses and dust deposits in the duct system Ensure that the correct transport velocity is achieved Correct ve...

Page 20: ...rth leakage circuit break er when the frequency converter is provided with an EMC filter The EMC filter function will make the earth leakage circuit breaker shut off the power Following the European s...

Page 21: ...ressed air line properly Connect a compressed air supply to the inlet see Fig ure 5 item 20 and Figure 9 items 6 and 7 Air pressure hoses are to be fitted together with electrical cables with straps a...

Page 22: ...rify the function of all emergency stop buttons alarms and signalling devices 6 2 Empty the collector bin WARNING Explosion risk Never use the unit without a bag WARNING Risk of personal injury Ensure...

Page 23: ...of the unit 12 Assemble the unit in reversed order 6 5 Check the filter cleaning function WARNING Risk of personal injury Crush hazard Pay attention when the com pressed air pressure cylinder and val...

Page 24: ...a label taped to the front of the PLC LOGO 8 soft ware is updated using an SD Card Follow the included instructions when the software needs to be updated To find the firmware and software revision num...

Page 25: ...ited If the PS cable is damaged press the Standby Running but ton to put the unit into Off mode and investigate the fault If necessary loosen the PS cable from the control unit see the electrical diag...

Page 26: ...n the system To check whether the sensor input is working disconnect the pressure sensor wire at terminal 2 and connect a jump er between terminals 2 and 1 Press the OK button on the PLC to reset the...

Page 27: ...ficient cleaning and premature filter clogging The CAS is connected to terminals X1 15 and X1 16 If no CAS is installed a jumper is linking the terminals to ensure that the CAS message is not displaye...

Page 28: ...memory FC Filter cleaning FCR Filter cleaning relay FCV Filter cleaning valve MFDPS Main Filter Differential Pressure Sensor MFDPS FC Main Filter Differential Pressure Sensor Filter Cleaning MFDPS Wr...

Page 29: ...FlexPAK SUV Solenoid upper valve TVFD Twin valve feed out device 29...

Page 30: ...kets Unit No Date Performed by Control items Result Application requirements limits Material chemical thermal reaction risk Radiation heat from surroundings Delivery checks Missing components Transpor...

Page 31: ...ir Compressed air valve Compressed air connected to the unit Incoming duct Incoming mains ground Accessories if applicable Signs and warnings Intended use marked or indicated Safe bag replacement desc...

Page 32: ...sult Result Result Previous service record Inspect clean outside the unit Remove dust deposits clean work area Remove corrosion by grinding apply primer and touch up paint Vacuum measure negative pres...

Page 33: ...aning valve check Filter bags visual check Filter bags check pressure drop perform ance The main filter replace Clean and dry air check GND1 Fan Incoming duct Incoming mains ground GND1 External mains...

Page 34: ...www nederman com...

Reviews: