VP1007-B / Installation manual
Version 01.000 / November 2020 / EN
13
Livestock Management
5 Commissioning
Caution
Before commissioning and handing over the system to the user, the installer must perform several checks
and tests to verify that the system functions flawlessly. Encountered issues and problems must be solved
first.
5.1 Testing inputs and outputs
The inputs and outputs of the VP1007-B can be tested with three tests:
1. Input/output test for Nedap feed motors.
2. Output test to check connected equipment like lights, valves or relays.
3. Input test to check connected equipment like switches and sensors.
The tests are performed using the menu options described in
VP1007-B reader menu overview (page 26)
Feed motor test
The feed motor test is a combination of an input and output test.
1. Go to
It
>
o1
to test the feed motor on the connector I/O 1.
When the test is finished, the test results are shown as a code on the display (blinking).
Code on the
display
Description motor test results
00
Motor run ok
01
Output already in use
02
No motor current measured
03
No input signal seen
06
Motor current too high for too long
08
Current still measured after test has stopped
09
Output voltage is stopped due to motor safeguard function
10
Output already in use
12
Motor current too low while running
13
Previous motor command finished, output still active
a. When the test result is not OK (higher than 00): Fix the problem and go to
It > dE
to reset the error.
2. If applicable, repeat step 1 for option
o2
,
o3
,
o4
or
o5
to test feed motors on connector I/O 2, I/O 3, I/O 4 or
I/O 5.
Output test
The output test is used to test connected equipment like light, valves or relay on the output connectors.
1. Go to
It
>
L1
to test the connected equipment on output 1.
The output is switched on.
2. Check if the green LED of the output is on.
A red blinking LED indicates an output error.
3. Go to
It
>
dE
to reset the output errors.
4. Check if the connected equipment is activated.