Nedap Invexs 170 Series Quick Install Sheet Download Page 2

 

 

EN 

Quick Install sheet |

 

Invexs 170 Readers Mifare Nedap dual technology readers

 

Version 12.0 

backside of the front. After making the connections, replace the front and tighten up the two 
screws at the bottom of the Invexs. 

4.

 

Connections 

Invexs is 

not 

hot-swappable, so when making or changing connections power must be switched 

Off

 

 

 

 

 

 
 

 

 

 

 

 

Cable shield 

must

 be connected to Power GND of Convexs (A2) and GND of  

           external device (or metal case). 

 

If connected to a 120kHz RF device (AEOS Nedap reader AEpack or XS device) the  

           power is supplied via the Convexs adapters (AX1014 for AEpacks, AB350 for XS    
           devices). Existing antenna cabling can then be reused for connecting the  
           ConveXS. 

 

UL*,NA* and BEEP are 

Open Collector to GND

           If the Convexs adapters are used, the original UL and NA signals are  

                  converted to the UL* and NA*. 

 

5.

 

LED Indicators Inside 

There are two LEDs available: 

Blue

 for Status (of application), 

Green 

for Identification (both 

visible through two small holes at the back side). 

 

 

 

 

 

 

 

 

 

6.

 

LED Indicators Front 

At the front a three colour LED is positioned at the middle of the Invexs  
Depending on the used configuration the function of these LEDs can differ: 

 

Green LED

:

   

Card is been authorised (UL LED)  

 

Red LED

:

    

Card is not authorised (NA LED), controller is stand-by 

 

Blue LED

:

 

Blinks fast; 

No configuration is available at this Invexs (present 

Configuration 

card

 or load 

Configuration

 first).

 

Continuously ON; 

Determined by configuration: E.g. Reader stand-by. 
(Blue LED is activated if UL is OFF and NA is more than 1 sec OFF.) 

 

Invexs 

Function 

Power / 

XSMOD 

Power in (12-30VDC) / 

XS modulator (120kHz) 

POWER GND/Shield 

Power Ground 

A (-) 

RS485 

B (+) 

RS485 

D0 

Wiegand Data 0 

D1 

Wiegand Data 1 

BEEP 

Beep input 

UL* 

UL LED input 

GND 

LED Common Ground 

10 

NA* 

NA LED input 

 

      R 

GND 

UL*/NA* / BEEP 

10 

10 

5

 

6

 

Invexs  

with display 

Invexs  

without display 

ID (green) 

Blinking  Card detected 

 

ST: STATUS (blue) 

Slow blinking  

Application running (operating) 

Fast blinking 

Downloading or error during 

loading 

2 short flashes 

Application present but not active 

3 short flashes 

No application present 

 