Select the charging program suitable for the type of house battery used based on the battery manufacturer's specifi-
cations, the information on the charging curves (see
). The specified charging times apply to an average ambient temperature of 20
°C.
Slide the DIP switches to the position shown in the table below to set the charging program for the respective
type of house battery.
Table 2: Charging curve configuration
Function
DIP switch po-
sition (gray)
Charging program
Maximum
voltage
(V
max
)
Maintenance volt-
age (V
maint
)
Desulfation volt-
age (V
des
)
1
2 3
ON
Lead gel batteries
Desulfation off
14.3
V
13.6
V
–
1
2 3
ON
Lead gel batteries
Desulfation on
14.3
V
13.6
V
15.8
V
1
2 3
ON
AGM batteries
Desulfation off
14.8
V
13.6
V
–
1
2 3
ON
AGM batteries
Desulfation on
14.8
V
13.8
V
15.8
V
1
2 3
ON
Wet batteries
Desulfation off
14.4
V
13.5
V
–
1
2 3
ON
Wet batteries
Desulfation on
14.4
V
13.5
V
15.8
V
12