10
Advanced Configuration
Input Configuration
Inputs on PN series controller can be configured to send notifications when the
input is opened or closed, only when they are closed, or only when they are
opened. This configuration is done through Base Station as follows:
Step 1:
Open Base Station, Select the Network Radio button on the Select
Connection window. Enter the IP address of the WiFi module in the IP address
text field. Enter the Port defined as the TCP Listener port in the WiFi module(by
default this is set to 2101). Then click the OK button below.
Step 2:
Base Station will communicate to the controller and display a window with
control software options. Select AD8 Relay Activator/Event Generator.
Step 3:
The AD8 Relay Activator/Event Generator window will now be
displayed. You will notice that each input can be tied to a function. The
functions are labeled for controlling relays but just know that rather than switch a
relay we will be triggering the notification. Inputs should only be set to
momentary or toggle at this time. If Input 1 function is being configured you may
set to to Momentarily Control Relay 1 or Toggle Relay 1. Do not set it to any
other feature or set it to a different relay number as this will cause confusion.
Step 4:
Once
settings are
configured
click the save
settings button
in the bottom
right corner to
save the
changes to the
controller.
Chapter
5