Boiler Room Design 

 

 

 

 

 

The internal diameter of the chimney must be sufficient enough for the amount of flue gases the 

chimney has to lead away. If the internal diameter is too small, this will prevent the smoke from exiting 

fast enough due to the large resistance in the chimney. This could cause the smoke to turn back; thus 

allowing for toxic fumes to enter into the house. Simultaneously, the pellet fuel may not be completely 

burned, due to the lack of oxygen for combustion. This can cause traces of tar like soot to sit in the 

chimney and create what is called creosote, which increases the risk of chimney fire.  
The chimney opening must also not be too large since cold air can enter the chimney from the top. 

When the chimney becomes cooled, condensation can occur and develop soot inside the chimney. 

Soot is mostly a cosmetic problem, because it can penetrate through the chimney and cause ugly 

brown splotches to appear on the walls inside the house. 
In addition, it is important that the chimney protrudes high enough above the roof so the smoke does 

not bother the surrounding houses. Environmental authorities have the possibility of prosecution if there 

are neighbors that complain about the smoke or odor. 
 

What signs are there, if the chimney is not working? 

Light sensor is sooty or melted. 

Smoke in the hopper. 

Warm drop shaft. 

Smoke billows out of the fan or boiler during startup.  

 
If you have any problems with your chimney, it is a good idea to keep  
a"diary“ of any draft problem; as draft problems are often associated  
with wind in certain directions. 
Wind blowing on one side of the house can cause under pressure on  
the other side of the house.  
Overpressure and under pressure will try to balance out-  
even through a chimney if possible. It is a good idea to ask your  
chimney sweeper about the size of the chimney and flues, the location of  
chimney cleaning doors, and whether it is required to have steps on the roof. 
He will also perform a fire prevention inspection. 
 

6. Air. 

The pellet boiler should be able to get enough air for combustion. This can be achieved if the pellet 

boiler is installed in a room which is equipped with a sliding window with an adjustment bracket,  an 

adjustable air vent from the outside, or by providing combustion chamber air through a duct from the 

outside. The area amount of the fresh air valve should generally be the same as the internal diameter 

of the chimney.  It should also be mounted on the same side as the chimney to compensate for any 

pressure differences. 

Note: 

that drum dryers, range hoods, or oil burner in the same room, all use high pressure blowers, 

that steal the air in the room! 
 

7. Water tap. 

There must be a tap in the boiler room. 
If the boiler output is less than 60 kW, a powder extinguisher can do it. 
(at least 5 kg) 
 

 

Summary of Contents for RTB

Page 1: ...NBE PELLET SYSTEMS RTB Ready to Burn EN303 5 2012 Class 5 approved by DTI Approved for expansion vessel Energy class AA Manufacturer NBE Production A S Brinken 6 10 ster Vr Denmark www nbe dk...

Page 2: ...e visible after going to the Extended Setup menu in the controller and enabling the Technical Setup to Yes This will allow you to make changes to the hidden menus for a 30 minute period Save this manu...

Page 3: ...cation of improper draft of the chimney all operation of your system must cease immediately and must remain so until a solution to the draft problem has been resolved Continuing operation may result i...

Page 4: ...on Minimum 24W 24W 20W 20W 34W 34W EN303 5 2012 Class 5 5 5 5 5 5 5 5 Controller Version V7 V7 V7 V7 V7 V7 V7 V7 Width mm only boiler 506 506 506 506 623 623 723 723 Depth mm 843 843 843 843 843 843 1...

Page 5: ...ons 10 kW burner Up to 60kg day 37 watt hour Weight 10kg 16 24kW burner Up to 110kg day 40 watt hour Weight 12kg 30kW burner Up to 150kg day 45 watt hour Weight 15kg 40kW burner Up to 200kg day 60 wat...

Page 6: ...ible material is covered with non flammable material If the distance is greater than 500 mm the distance requirement is typically satisfied 3 Floor Floors should consist of or be covered with non comb...

Page 7: ...ty or melted Smoke in the hopper Warm drop shaft Smoke billows out of the fan or boiler during startup If you have any problems with your chimney it is a good idea to keep a diary of any draft problem...

Page 8: ...t oil for oil burners The floor must be kept free of spilled fuel dust and combustible waste as well as waste from other activities in the room Any burning embers must be extinguished with water and t...

Page 9: ...degrees Buildings with a roof slope that is less than 20 degrees and is adjacent to another building Buildings with a slope greater than 20 degrees Buildings with a slope greater than 20 degrees and h...

Page 10: ...oil is small Heat for the house is supplied while hot water is being produced 3 DHW with 3 way valve Typically used when the water heater is large and when the surface coil is large The house is not s...

Page 11: ...over the boiler must be installed with a cleanout door and must be 500 mm in length above the boiler as to allow for easy dismounting of the controller cassette located at the back of the boiler Inst...

Page 12: ...t 1300 mm Depth 845 mm Pellet Capacity 220 kg Compatible with RTB sizes 10 16 30 kW 320kg Hopper Width 700 mm Width Boiler Hopper 806 mm Height 1300 mm Depth 845 mm Pellet Capacity 320 kg Compatible w...

Page 13: ...gure your vacuum transport Big bag Throw the mole in the bag Easy way to transport 1 ton Flat bottom hopper Take advantage of your maximum space Minimizes ceiling height requirements V bottom hopper T...

Page 14: ...Wiring Diagram...

Page 15: ...Wiring Diagram...

Page 16: ...for equipment EKSTRA 3 PE N L9 Boiler Compressor Valve 1 EKSTRA 3 PE N L10 Boiler Compressor Valve 2 BUS GRD TX RX Expansion module ILT V1 V V2 O2 controller KONTAKT K K1 External ON OFF KONTAKT K K2...

Page 17: ...or INCLUDED WITH RTB Compressor Clean the burner head efficiently with high pressure With low noise compressor Solar heating Use the pellet burner controller to run your solar system External temp sen...

Page 18: ...roller screen If you do not have the possibility of a direct cable connection these adapters pictured on right can be used They can establish a connection to your router through your household power c...

Page 19: ...kerkontrol Internet Connection 6 Stokercloud dk will display the location of your system via a drop pin on the stokercloud map If you do not want others to see the exact location of your system simply...

Page 20: ...E will contact you by e mail and ask your permission to make operational changes If permission is granted to NBE we will monitor your systems operational graphs and burner reaction pattern and make ad...

Page 21: ...weight II Adjusting the Blower 1 Turn on the system by pressing the ON OFF button on the controller 2 Go to the Regulation menu set Min power 100 Max power 100 This will lock output to 100 power Allo...

Page 22: ...faces inside the boiler must be brushed clean from any deposits and the ash can must be emptied When empting the ash can pay special attention to any build up of ash in the rear smoke chamber and flue...

Page 23: ...ice audit of your boiler once a year by an authorized dealer technician in order to prevent unexpected downtime Hours ON OFF RESET DATE 43 External gear 15000 ON NEJ 31 12 12 35 Internal gear 15000 ON...

Page 24: ...grate is fitted wrong Mount it correctly Too high chimney draft Install a draft stabilizer in the chimney Set electric ignition power up Reduce the fan speed during ignition Stopped fan Check if the f...

Page 25: ...ate with pipe insulation Too many electric ignitions Flow in the system is fluctuating Set the pressure controlled circulation pump to fixed pressure External thermostat unstable Set External wait up...

Page 26: ...Hits the smoke boiler surfaces under 47C degrees it starts condensing 7 Open bypass in the boiler applicable only on BS1016 BS2030 BS4050 Release the smoke before the last smoke cooler 15C degrees in...

Page 27: ...de by agreement with NBE To the extent that NBE is liable to the purchaser NBE s liability is limited only to direct loss and not to damages incurred by connected equipment and or indirect damage loss...

Page 28: ...CE Declaration of Conformity...

Page 29: ...d Blower high Comments Date Weighing g kW low kW kW high kW Blower low Blower mid Blower high Comments Date Weighing g kW low kW kW high kW Blower low Blower mid Blower high Comments Date Weighing g k...

Reviews: