Catalogue number:
AN
□□□□□□
AS
Air Circuit Breaker 1600-5000 70-85kA
AS
□□□□□□
Motor
Charge the closing spring of a circuit breaker by the external
power source. Without the external power source, the spring must
be charge manually.
Operating voltage range (IEC 60947)
85%~110%Vn
Input voltage (V)
DC 24~30V AC/DC 48~60V
AC/DC 100~130V
AC/DC 200~250V AC 380V
AC 440~480V
Load curent (Max.)
5A
3A
1A
0.5A
0.3A
0.3A
Starting current (Max.)
Load rpm (Motor)
Charge time
Dielectric strength
Using temperature range
Using humidity range
Charge switch
10A at 250VAC
15000 ~ 19000 rpm
Less than 5sec.
2kV/min
-20°~ 60°
Max. RH 80% (No dew condensation)
5 times of load current
Type
AN, AS-D
AN, AS-E
AS-F
AS-G
Endurance
20000
15000
10000
10000
N.A.W. Controls Pty. Ltd.
Telephone: (03) 9464 6555
www.nawcontrols.com.au
LS ACB AS & AN range
June 2020