Oxygen detectors 

 URS20SI 

05/10/2020 

Gas detection systems for industrial environments 

6/8

 

 

Electrical installation of 
the optional relay card 

 

Selecting the type of 
contact on the terminal 
board: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Configuring the relay 
operating mode:

 

After mechanically installing the relay card, it is necessary to configure it electrically, 
selecting the relay operating mode and the type  of  contact desired on the terminal 
board (NC or NO). 

A pair of extractable terminals is available for each relay; the type of contact (NC or 
NO) to be associated with them can be selected using the 

JP1…JP4

 jumpers. 

 
NC or NO contact of pre-alarm relay 
NC or NO contact of 1

st

 THRESHOLD relay 

NC or NO contact of 2

nd

 THRESHOLD relay 

NC or NO contact of FAIL relay 

 

DL1 (yellow),   Sensor FAIL 

DL2 (red),  2

nd

 alarm THRESHOLD 

DL3 (red),  1

st

 alarm THRESHOLD

 

DL4 (red),   Pre-alarm  

 
Selecting the terminal contact: 
 
 
 

NC                         NO 

 
 
 
To  set  the  operating  mode  of  the  relays:  for  direct  (relay  energised  by  event)  or 
reverse (relay energised with no event), it is necessary to use the 6th selector of the 
DIP switch at 

S1

; in particular: 

 
 

                                              direct operating mode  

reverse operating mode 

 

Checklist after 
mechanical and 
electrical installation 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The  sensors  are  factory  calibrated  so  they  normally  do  not  require  any  other 
calibration once installed. Still, after installation, an operational check of the sensors 
is recommended. 
The detector will enter a 2-minute warm-up phase after power-up. 
After this time, the sensor will switch to normal operating mode, but it will take about 
2 hours before it reaches top performance level. 
When the detector is operating, a gas response check should be carried out using 
the 

TUL40..

 gas calibration kit. This kit contains: 

-

  1 calibration gas cylinder: 4% of O

2

; (see kit part numbers on the specific technical 

data sheet) 

-

  pressure valve and flow regulator 

-

  sensor body adapter 

-

  about 2 metres of hose between cylinder and adapter. 

During the test, check the output current, the status of the LED visible on the outside 
of  the  enclosure  and,  if  present,  the  status  of  the  LEDs  on  the  relay  card  before 
closing the housing 

The  LED  on  the  housing  and  the  4...20mA  output  have  the  following  operating 
meaning: 

Sensor status 

4...20mA Output 

Status LED on housing 

WARM-UP 

2mA 

Flashing at 2Hz frequency 

OPERATING 

4...20mA 

0,10,20mA for 

threshold 

applications 

1 flash about every 10 sec. 

PRE-ALARM 

2 flashes about every 5 sec. 

1

st

 ALARM THRESHOLD 

3 flashes about every 5 sec. 

2

nd

 ALARM THRESHOLD 

4 flashes about every 5 sec. 

SENSOR FAIL 

22mA 

Steady 

  D   |   

 

  B   |   

 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

Summary of Contents for EsiWelma Sensigas URS20SI

Page 1: ...ore in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SI sensors can be used...

Page 2: ...esholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up to 200 at 12Vd...

Page 3: ...nstructions for location of the detectors The detectors must be installed 1 where accidental gas leakages are possible 2 at least 1 5m away from heat sources or from vent holes 3 not in spaces where v...

Page 4: ...or are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as sho...

Page 5: ...ep 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection slot flex...

Page 6: ...nstallation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended The dete...

Page 7: ...return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 handheld t...

Page 8: ...in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Replacement date Routine checks To be filled in by Installer Se...

Reviews: