3
Venting
>
Electrical Connections
>
Vent Termination Options
Indoor Horizontal Vent Termination
Vertical vent termination
12" (300mm) min.
12" (3
00mm
) min.
Interior view
Intake Air
Exhaust Gas
12" (300 mm) min.
12" (3
00 mm
) min.
Exterior view
12" min. from any
obstruction above,
below, left, or right
12" (300 mm) min.
12" (300 mm) min.
36" (900 mm) min.
Sidewall vent termination
Concentric Vent Termination
Sidewall installation
Combustion Air
Combustion Air
1" (25mm) min
Maintain 12" min.
clearance above
highest anticipated
snow level or grade.
Vent
Roof installation
Image of outdoor vent cap
Vent
Vent
Combustion Air
Maintain 12" min.
(18" min. for Canada)
clearance above
highest anticipated
snow level maximum
of 24" above roof.
Combustion
Air
Side
Bottom
Intake Air
Exhaust Gas
Top
Front
Side
Back
Venting Length
4” pipe venting
3” pipe venting
8
1
3
7
2
Maximum Length 150'
Maximum number
of elbows: 8
3-to-4 inch
6
1
3
4
5
2
Maximum number
of elbows: 6
Maximum Length 70"
·
90˚ elbow = 5 linear feet of venting
·
45˚ elbow = 3 linear feet of venting
·
90˚ elbow = 5 linear feet of venting
·
45˚ elbow = 3 linear feet of venting
Exhaust Vent Piping Materials
Venting requirements differ in the US and Canada. Consult the following chart or the
most recent edition of ANSI Z223.1/NFPA 54 or CAN/CGA B149.1, as well as all
applicable local codes and regulations when selecting vent pipe materials. Do not use
cellular core PVC (ASTM F891), cellular core CPVC, Radel® (polyphenolsulfone) for the
exhaust vent.
Navien recommended venting materials
Locale
Recommended Vent Materials
USA
·
PVC/CPVC Schedule 40 or 80 (Solid Core) - UL1738-certified materials are
approved for use
·
Approved Polypropylene*
·
Approved Stainless Steel
Canada*
·
Type BH Special Gas Vent Class IIA (PVC)
·
Type BH Special Gas Vent Class IIB (CPVC)
·
Type BH Special Gas Vent Class IIC (Polypropylene/Stainless Steel)
* Refer to the manufacturer’s literature for detailed information on approved vent materials.
** For installation in Canada, field-supplied plastic vent piping must comply with CAN/CGA B149.1 (latest
edition) and be certified to the Standard. For Type BH Gas Venting Systems, ULC-S636. Components of
this listed system must not be interchanged with other vent systems or unlisted pipes or fittings. All
plastic components and specified primers and glues of the certified vent system must be from a single
system manufacturer and must not be intermixed with another system manufacturer’s parts. The
supplied vent connector and vent termination are certified as part of the water heater.
Remote Controller Connection
Power Connection
120 V AC 60 Hz
Min. 2 Amp current with proper
grounding
CAUTION
Using abnormally high or low AC
voltage may cause abnormal operation,
thereby causing fire which reduces the
life expectancy of this product.
CAUTION
Disconnect the power to
the water heater before
installing the remote
controller.
Safety
DO NOT touch
the power
cord with wet
hands.
DO NOT allow
the water
heater to be
exposed to
excessive
amounts of
water.
Confirmation of DIP Switch Settings
1
2
ON
·
2-switch Panel:
Switch
Function
Setting
2
Temperature Lock
Temperature can be set.
OFF
Temperature cannot be set.
ON