5.2.24 615Error
Error occurrence conditions and check items
Error
Description
E615 error
Abnormal signal input by PCB.
Check items
1. Turn the POWER RESET switch OFF then ON (or unplug and replug the power supply.
2. If the system still displays E615, replace the main PCB.
5.2.25 740Error
Error conditions and Check Items
Error
Description
E740
Abnormal outdoor sensor
If an error (under 2.2kΩ or over 122.2kΩ) in the outdoor sensor is detected continuously for
3 seconds, The system displays the error message E740 on the front panel. If this occurs, the
boiler changes the control mode from Reset Curve Mode to Normal Mode.
Check items
1. Check the parameter setting. (refer to page 49-51)
2. Check the outdoor sensor
Is the Outdoor sensor
installed properly?
Is the outdoor thermistor
normal?
Check connecter
(#1 and #2 of CN11)
Change the Outdoor Reset Control
Mode setting (refer to page 49-51).
Replace the outdoor thermistor.
No
No
Yes
Yes