71
Venting for Combustion Air
Ref Description
Canadian Non-Direct
Vent Installations
1
US Non-Direct Vent
Installations
2
A
Clearance above grade, veranda, porch, deck,
or balcony
12 in (30 cm)
12 in (30 cm)
B
Clearance to window or door that may be
opened
36 in (91 cm)
48 in (120 cm) below or
to side of opening; 12 in
(30 cm) above opening
C
Clearance to permanently closed window
*
*
D
Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the
terminal
*
*
E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
*
*
G
Clearance to inside corner
*
*
H
Clearance to each side of center line extended
above meter/regulator assembly
36 in (91 cm) within
a height 15 ft
(4.57 m) above the meter/
regulator assembly
*
I
Clearance to service regulator vent outlet
36 in (91 cm)
*
J
Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
36 in (91 cm)
48 in (120 cm) below or
to side of opening; 12 in
(30 cm) above opening