GV20/GV15 INSTALLATION MANUAL
CONNECTING AC POWER
VERSION 5.0 2021-03-01
PAGE 2.5.1
SECTION 2.5: CONNECTING AC POWER
Connect ac power to the transmitter as follows:
NOTE
: The transmitter’s internal wiring is factory configured to operate from the customer’s desired ac
power source. Ensure that the ac configuration label on the transmitter agrees with the main ac power
source voltage that you are connecting.
1.
Switch off the main ac power at the service entrance.Remove the rear filter panel (1/4-turn
fasteners) from the transmitter.
2.
Select the appropriate wire size for your main ac power cables. See the GV20/GV15 Pre-Installation
Manual for assistance. Ensure the ground wire is insulated, so it does not contact the transmitter
cabinet at any location other than the safety ground stud.
NOTE
: Some types of cable (e.g., TEC cable) have an exposed ground wire. In such cases, Nautel
recommends that you sleeve (insulate) the ground wire.
3.
Route the main ac power cables in a suitable conduit, from the ac disconnect switch to the top of
the transmitter.
4.
Punch the appropriate size hole in the ac entry box as follows (see
Remove the top cover from the ac entry box. It is secured using four M4 screws and has three pre-cut,
1/4-inch diameter holes.
Use a chassis punch tool (e.g., Greenlee, etc.) to punch the desired size hole(s) in the top cover. Make
sure the ac input cables will pass safely through the hole(s).
Re-install the top cover on the ac entry box using four M4 screws.
5.
Verify that the station reference ground is connected to the ground stud at the back of the cabinet.
See
Section 2.4, “Connecting to Station Reference Ground” on page 2.4.1
6.
Route the ac power cables through the hole(s) punched in the top of the ac input entry box to the
ac input terminal block (TB1) (see
).
NOTE
:
The GV20/GV15 contains pre-installed ferrite toroids for internal ac wiring. For this reason, additional
ferrite toroids should not be required for the ac input wiring. The ancillary kit contains ferrite toroids (Nautel
Part # LP32) for use with the ac input wiring, if desired.
7.
Temporarily remove the rear cover from the ac input entry box (four M4 screws), noting the cover is
secured to the box with a bonding (ground) wire, which should not be disconnected.
WARNING! ENSURE THAT WIRING SIZES ARE APPROPRIATE. AC WIRING
MUST BE INSTALLED BY A QUALIFIED, LOCALLY-CERTIFIED ELECTRICIAN.
Summary of Contents for GV20
Page 2: ......
Page 4: ......
Page 8: ...GV20 GV15 INSTALLATION MANUAL PAGE 2 VIII VERSION 5 0 2021 03 01...
Page 18: ...GV20 GV15 INSTALLATION MANUAL UNPACKING AND POSITIONING PAGE 2 2 8 VERSION 5 0 2021 03 01...
Page 24: ...GV20 GV15 INSTALLATION MANUAL INSTALLING OPTIONS PAGE 2 3 6 VERSION 5 0 2021 03 01...
Page 36: ...GV20 GV15 INSTALLATION MANUAL INSTALLING PROGRAM INPUTS PAGE 2 7 4 VERSION 5 0 2021 03 01...
Page 50: ...GV20 GV15 INSTALLATION MANUAL COMMISSIONING PAGE 2 9 8 VERSION 5 0 2021 03 01...
Page 54: ...GV20 GV15 INSTALLATION MANUAL PARTS AND TOOLS PAGE 2 10 4 VERSION 5 0 2021 03 01...
Page 64: ...GV20 GV15 INSTALLATION MANUAL LIST OF TERMS PAGE 2 12 2 VERSION 5 0 2021 03 01...
Page 65: ......