National Instruments NI cRIO-9036 Getting Started Manual Download Page 15

Table 4.

 STATUS LED Indicators

LED

Color

LED Pattern

Indication

 

 

 

Yellow

Blinks twice and

pauses

The cRIO-9036 is in safe mode. Software is not installed,
which is the factory default state, or software has been
improperly installed on the cRIO-9036.

An error can occur when an attempt to upgrade the software
is interrupted. Reinstall software on the cRIO-9036. Refer
to the 

Measurement & Automation Explorer (MAX) Help

 for

information about installing software on the cRIO-9036.

Blinks three times

and pauses

The cRIO-9036 is in user-directed safe mode, or the
cRIO-9036 is in install mode to indicate that software is
currently being installed.

This pattern may also indicate that the user has forced the
cRIO-9036 to boot into safe mode by pressing the reset
button for longer than five seconds or by enabling safe
mode in MAX. Refer to the 

Measurement & Automation

Explorer (MAX) Help

 for information about safe mode.

Blinks four times

and pauses

The cRIO-9036 is in safe mode. The software has crashed
twice without rebooting or cycling power between crashes.

Continuously

blinks

The cRIO-9036 has not booted into NI Linux Real-Time.
The cRIO-9036 either booted into an unsupported operating
system, was interrupted during the boot process, or detected
an unrecoverable software error.

On momentarily

The cRIO-9036 is booting. No action required.

Red

Continuously

blinks

This indicates a hardware error. An internal power supply
has failed. Check front-panel I/O and C Series module
connections for shorts. Remove any shorts and cycle power
the cRIO-9036. If the problem persists, contact NI.

Off

The cRIO-9036 is in run mode. Software is installed and the
operating system is running.

NI cRIO-9036 Getting Started Guide

  | 

© National Instruments

  | 

15

Summary of Contents for NI cRIO-9036

Page 1: ...w to begin using the National Instruments cRIO 9036 Safety Guidelines Caution Do not operate the cRIO 9036 in a manner not specified in this document Product misuse can result in a hazard You can comp...

Page 2: ...nclosure rated to at least IP54 as defined by IEC EN 60079 15 Caution Do not insert or remove SD cards unless power has been switched off or the area is known to be nonhazardous Caution The USB host p...

Page 3: ...ral device or test object or if the product is used in residential or commercial areas To minimize interference with radio and television reception and prevent unacceptable performance degradation ins...

Page 4: ...ts In addition take precautions when designing selecting and installing measurement probes and cables to ensure that the desired EMC performance is attained Preparing the Environment Ensure that the e...

Page 5: ...ce Drivers Media 5 Getting Started Guide Installing Software on the Host Computer Before using the cRIO 9036 you must install the following application software and device drivers on the host computer...

Page 6: ...n the C Series module 3 Align the C Series module with a slot and seat it in the slot until the latches lock in place Removing C Series Modules Verify that power is not connected to the I O connector...

Page 7: ...rminal to the grounding electrode system of the facility What to Use Ring lug Wire 1 3 mm2 16 AWG or larger Screwdriver Phillips 2 What to Do Complete the following steps to ground the cRIO 9036 1 Att...

Page 8: ...036 has a primary power input V1 and a secondary power input V2 The POWER LED on the cRIO 9036 indicates which power input is in use as shown in the following table Table 2 POWER LED Indicators LED Co...

Page 9: ...tive leads of the power supply as shown in the following figure Figure 3 Installing a Ferrite on the Power Leads 2 1 1 Pass the leads through the ferrite twice leaving 50 mm to 75 mm 2 in to 3 in betw...

Page 10: ...cRIO 9036 When you power on the cRIO 9036 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then the STATUS LED blinks twice every few...

Page 11: ...ber such as NI CRIO 9036 1856AAA Setting a System Password Complete the following steps to set a system password Note The default username for the cRIO 9036 is admin There is no default password for t...

Page 12: ...if you plan on using the cRIO 9036 without the LabVIEW FPGA Module Tip You can use this wizard at anytime to install additional software 7 Click Next 8 Verify that the summary of software to install i...

Page 13: ...System IP Configuration 1 Put the cRIO 9036 in safe mode and enable the RS 232 serial port by holding the RESET button down for 5 seconds The STATUS LED starts blinking three times every few seconds...

Page 14: ...d RESET button for 5 s Press and hold RESET button for 5 s Run Mode Safe Mode Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold...

Page 15: ...r longer than five seconds or by enabling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9036 is in safe m...

Page 16: ...eshooting and application development self help resources to email and phone assistance from NI Application Engineers Visit ni com services for NI Factory Installation Services repairs extended warran...

Page 17: ...create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For telephone support outside the United States visit the Worldwide Offices section of ni com niglobal to access the bran...

Page 18: ...party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain rel...

Reviews: