Special Conditions for Hazardous Locations Use

in Europe and Internationally

The NI 9425 with spring terminal has been evaluated as Ex nA IIC T4 Gc equipment

under DEMKO 12 ATEX 1202658X and is IECEx UL 14.0089X certified. The NI 9425 with

DSUB has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO 03 ATEX

0324020X and is IECEx UL 14.0089X certified. Each NI 9425 is marked   II 3G and is

suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤

Ta ≤ 70 °C. If you are using the NI 9425 in Gas Group IIC hazardous locations, you

must use the device in an NI chassis that has been evaluated as Ex nC IIC T4, Ex IIC

T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.

Caution

 Transient protection shall be provided that is set at a level not

exceeding 140% of the peak rated voltage value of 85 V at the supply

terminals to the equipment.

Caution

 The system shall only be used in an area of not more than

Pollution Degree 2, as defined in IEC/EN 60664-1.

Caution

 The system shall be mounted in an ATEX/IECEx-certified

enclosure with a minimum ingress protection rating of at least IP54 as

defined in IEC/EN 60079-15.

Caution

 The enclosure must have a door or cover accessible only by the

use of a tool.

© National Instruments

3

NI-9425 Getting Started