Safety Guidelines for Hazardous Voltages

Caution

 Ensure that hazardous voltage wiring is performed only by

qualified personnel adhering to local electrical standards.

Caution

 Do not mix hazardous voltage circuits and human-accessible

circuits on the same module.

Caution

 Ensure that devices and circuits connected to the module are

properly insulated from human contact.

Note

 When module terminals are hazardous voltage LIVE (>42.4 V

pk

/

60 V DC), you must ensure that devices and circuits connected to the

module are properly insulated from human contact. You must use the

NI-9927 connector backshell kit with the NI-9263 with screw terminal and

the NI-9981 connector backshell kit with the NI-9263 with spring terminal

to ensure that the terminals are not accessible.

Safety Voltages

Connect only voltages that are within the following limits:

Channel-to-channel

None

Channel-to-earth ground

Continuous

250 V RMS, Measurement Category II

Withstand

2,300 V RMS, verified by a 5 s dielectric withstand test

Safety Guidelines for Hazardous Locations

The NI-9263 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous

locations; Class I, Zone 2, AEx nA IIC T4 Gc and Ex nA IIC T4 Gc hazardous locations;

and nonhazardous locations only. Follow these guidelines if you are installing the

ni.com

4

NI-9263 Getting Started

Summary of Contents for NI 9263

Page 1: ...NI 9263 Getting Started 2022 07 06...

Page 2: ...afety Guidelines for Hazardous Locations 4 Electromagnetic Compatibility Guidelines 6 Special Conditions for Marine Applications 6 Preparing the Environment 7 NI 9263 Pinout 7 Load Connections 8 High...

Page 3: ...s in the system might not meet the same safety ratings Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Safety Guidelines Cauti...

Page 4: ...se the NI 9927 connector backshell kit with the NI 9263 with screw terminal and the NI 9981 connector backshell kit with the NI 9263 with spring terminal to ensure that the terminals are not accessibl...

Page 5: ...ial Conditions for Hazardous Locations Use in Europe and Internationally The NI 9263 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO 07ATEX 0626664X and is IECEx UL 14 0089X certified Each...

Page 6: ...peripheral device or test object or if the product is used in residential or commercial areas To minimize interference with radio and television reception and prevent unacceptable performance degrada...

Page 7: ...perating temperature IEC 60068 2 1 IEC 60068 2 2 40 C to 70 C Operating humidity IEC 60068 2 78 10 RH to 90 RH noncondensing Pollution Degree 2 Maximum altitude 2 000 m Indoor use only Note Refer to t...

Page 8: ...al Descriptions Load Connections NI 9263 COM AO Load High Vibration Application Connections If your application is subject to high vibration NI recommends that you follow these guidelines to protect c...

Page 9: ...tion downloads and troubleshooting and application development self help such as tutorials and examples Visit ni com services to learn about NI service offerings such as calibration options repair and...

Reviews: