NI-9234 in a potentially explosive environment. Not following these guidelines may

result in serious injury or death.

Caution

 Do not disconnect I/O-side wires or connectors unless power has

been switched off or the area is known to be nonhazardous.

Caution

 Do not remove modules unless power has been switched off or

the area is known to be nonhazardous.

Caution

 Substitution of components may impair suitability for Class I,

Division 2, or Zone 2.

Caution

 The system must be installed in an enclosure certified for the

intended hazardous (classified) location, having a tool secured cover/door,

where a minimum protection of at least IP54 is provided.

Caution

 For Division 2 and Zone 2 applications, connected signals must

be within the following limits.

Capacitance

0.2 µF maximum

Special Conditions for Hazardous Locations Use in Europe and

Internationally

The NI-9234 has been evaluated as Ex nA IIC T4 Gc equipment under

DEMKO 07ATEX 0626664X and is IECEx UL 14.0089X certified. Each NI-9234 is marked

 II 3G and is suitable for use in Zone 2 hazardous locations, in ambient

temperatures of -40 °C ≤ Ta ≤ 70 °C . If you are using the NI-9234 in Gas Group IIC

hazardous locations, you must use the device in an NI chassis that has been

evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.

ni.com

4

NI-9234 Getting Started

Summary of Contents for NI 9234

Page 1: ...NI 9234 Getting Started 2022 07 06...

Page 2: ...5 Special Conditions for Marine Applications 5 Preparing the Environment 6 Connecting the NI 9234 6 Signal Descriptions 7 Connecting Floating Differential Signals 7 Connecting Grounded Differential Si...

Page 3: ...lisation L utilisation du produit de toute autre fa on que celle sp cifi e risque de l endommager et de compromettre la protection de s curit int gr e Safety Voltages Connect only voltages that are wi...

Page 4: ...tool secured cover door where a minimum protection of at least IP54 is provided Caution For Division 2 and Zone 2 applications connected signals must be within the following limits Capacitance 0 2 F...

Page 5: ...ated in the product specifications These requirements and limits provide reasonable protection against harmful interference when the product is operated in the intended operational electromagnetic env...

Page 6: ...signing selecting and installing measurement probes and cables to ensure that the desired EMC performance is attained Preparing the Environment Ensure that the environment in which you are using the N...

Page 7: ...ignal Description AI Provides DC excitation when enabled and positive input signal connection AI Provides excitation return path and signal ground reference Table 1 Signal Descriptions Connecting Floa...

Page 8: ...of reading per ohm of AI impedance The common mode bias current causes an error only with grounded sources and is not an issue with floating signal sources For best accuracy use low impedance leads wh...

Page 9: ...port resources including documentation downloads and troubleshooting and application development self help such as tutorials and examples Visit ni com services to learn about NI service offerings such...

Reviews: