and nonhazardous locations only. Follow these guidelines if you are installing the

NI-9232 in a potentially explosive environment. Not following these guidelines may

result in serious injury or death.

Caution

 Do not disconnect I/O-side wires or connectors unless power has

been switched off or the area is known to be nonhazardous.

Caution

 Do not remove modules unless power has been switched off or

the area is known to be nonhazardous.

Caution

 Substitution of components may impair suitability for Class I,

Division 2, or Zone 2.

Caution

 The system must be installed in an enclosure certified for the

intended hazardous (classified) location, having a tool secured cover/door,

where a minimum protection of at least IP54 is provided.

Caution

 For Division 2 and Zone 2 applications, connected signals must

be within the following limits.

Capacitance

0.2 µF maximum

Special Conditions for Hazardous Locations Use in Europe and

Internationally

The NI-9232 has been evaluated as Ex nA IIC T4 Gc equipment under

DEMKO 12ATEX 1202658X and is IECEx UL 14.0089X certified. Each NI-9232 is marked

 II 3G and is suitable for use in Zone 2 hazardous locations, in ambient

temperatures of -40 °C ≤ Ta ≤ 70 °C. If you are using the NI-9232 in Gas Group IIC

hazardous locations, you must use the device in an NI chassis that has been

evaluated as Ex nC IIC T4, Ex IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.

ni.com

4

NI-9232 Getting Started

Summary of Contents for NI-9232

Page 1: ...NI 9232 Getting Started 2022 07 06...

Page 2: ...lity Guidelines 5 Cable Requirements for EMC Compliance 6 Special Conditions for Marine Applications 7 Preparing the Environment 7 Connecting the NI 9232 8 Connecting Signal Sources 8 Wiring for High...

Page 3: ...documentation d utilisation L utilisation du produit de toute autre fa on que celle sp cifi e risque de l endommager et de compromettre la protection de s curit int gr e Safety Voltages Connect only v...

Page 4: ...ed hazardous classified location having a tool secured cover door where a minimum protection of at least IP54 is provided Caution For Division 2 and Zone 2 applications connected signals must be withi...

Page 5: ...e reasonable protection against harmful interference when the product is operated in the intended operational electromagnetic environment This product is intended for use in industrial locations Howev...

Page 6: ...duct installation instructions Refer to the NI 9232 product page on ni com for purchasing information about clamp on ferrite beads Notice To ensure the specified EMC performance the length of all I O...

Page 7: ...he EMC requirements for marine applications install the product in a shielded enclosure with shielded and or filtered power and input output ports In addition take precautions when designing selecting...

Page 8: ...single terminal on the NI 9232 with screw terminal Each channel has a terminal to which you can connect a signal source The AI terminal of the connector provides the DC excitation when enabled and the...

Page 9: ...ource Integrated Electronic Piezoelectric IEPE Sensors The NI 9232 provides an IEPE excitation current for each channel to measure the IEPE sensors Typical IEPE sensors have a case that is electricall...

Page 10: ...earn about NI service offerings such as calibration options repair and replacement Visit ni com register to register your NI product Product registration facilitates technical support and ensures that...

Reviews: