The rest of the setup process requires assistance from a server administrator with

permission to add and configure devices in the NI InsightCM web application: 

1. Ask the server administrator to add the device to the NI InsightCM web application.

2. Ask the administrator if you need to manually provision the device with an IP address

    or credentials. If so, obtain a USB drive that contains the connection information file.

Wire sensors to C Series modules installed in the device chassis.

In a CMS-9036 device, only connect tachometers to the module in slot 1.

In an IR-3120 device, you only need to connect cameras.

22

When you apply power to the controller, it starts up:

1. The POWER LED is lit while the device is powered on to indicate that the power

   supply connected to the chassis is adequate. 

2. After the device boots, the USER1 LED flashes steadily to indicate normal operation.

If you have access to the NI InsightCM web application, make sure the device connects to

NI InsightCM Server successfully:

1. Browse to 

http://

serverHostname

:82

 in a web browser on the same network             

    as NI InsightCM Server. 

 

2. Log in to the NI InsightCM web application. 

 

3.

 

Expand the 

Configuration 

pull-down menu and click

 Devices

. Verify the device appears 

with a status of Online.


33

1. Connect the chassis grounding terminal to the grounding electrode system of your facility.

2. Connect the positive lead of the power source to either V terminal on the power  

    connector plug, and the negative lead to the C terminal.

If instructed by the server administrator, complete the following steps to manually

provision the device:

1. Insert the USB drive with the connection information in the USB port on the controller.

2. The USER1 LED lights solid, which indicates that the device is reading network and

    connection properties.

You can remove the USB drive when the USER1 LED returns to blinking steadily.

44

55

66

Verify Device Is Added

to Server

Connect Sensors 

to Modules

Provision Device

Verify Connectivity

Verify Controller Power

Connect to Power

77

Caution

  The C terminals are internally connected to each other.

For instructions for these tasks, refer to the

 Getting Started with NI

Monitoring Devices and NI InsightCM 

TM

 Server

 document

(

gettingStarted_InsightCMServer.pdf

). To access this document, visit 

ni.com/info

 and enter 

insightcmdocs

 or browse for the file on the

NI InsightCM Server USB installation media.

Refer to the module operating instructions manual for signal connections. 

For a list of these documents, visit 

ni.com/info

 and enter 

insightcmdocs

.