Table 10. STATUS LED Indications
LED Color
LED State
Indication
Yellow
OFF
The IC-317x initialized successfully and is ready for use.
2 blinks
(RT only) The device has automatically booted into safe
mode. This occurs when there is no software installed, which
is the out-of-box state, or the device has detected an error in
its software. Reinstall software on the IC-317x.
3 blinks
(RT only) The IC-317x has booted into safe mode.
4 blinks
(RT only) The IC-317x has experienced two consecutive
software exceptions. The IC-317x automatically restarts after
an exception. After the second exception, the IC-317x
remains in the exception state, alerting you to resolve the
problem. Reinstall software on the IC-317x or contact
National Instruments.
Continuous
blink
(RT only) The IC-317x has not booted into NI Linux Real-
Time. The controller either booted into an unsupported
operating system, was interrupted during the boot process, or
detected an unrecoverable software error.
ON
(RT only) The IC-317x is booting up.
(Windows only) An internal drive is being accessed.
Red
Continuous
blink
This indicates a hardware error. An internal power supply has
failed. Check front-panel I/O connections for shorts. Remove
any shorts and cycle power to the IC-317x. If the problem
persists, contact National Instruments.
Related Information
Safe Mode
on page 19
Safe Mode
on page 19
User LEDs
You can define the USER1 and USER FPGA1 LEDs to meet the needs of your application.
The following table describes the USER1 and USER FPGA1 LED indicators.
IC-317x User Manual
|
© National Instruments
|
17