background image

6.

Click 

OK

.

7.

Click 

Change Password

.

8.

Enter and re-enter a new password.

9.

Click 

OK

.

10. Click 

Save

.

11. Click 

OK

 to confirm you are changing the password.

Caution

 

NI cannot recover lost system passwords. If you forget the password,

you must contact NI and reformat the controller.

Configuring the IC-3121 for Windows

The Windows version of the IC-3121 ships preloaded with Windows Embedded Standard 7
64-bit. Complete this section if you are using the Windows version of the IC-3121.

Connecting the IC-3121 to a Network

Complete the following steps to connect the device to a network.
1.

Connect one end of an Ethernet cable to the network port on the device.

2.

Connect the free end of the cable to an Ethernet hub or other network device.

3.

Verify the ACTIVITY/LINK LED on the port is on or blinking.

By default, the operating system automatically attempts to connect to the network using
DHCP. If it is unable to initiate a DHCP connection, it connects to the network with a link-
local IP address (169.254.x.x).

Installing the NI Industrial Controller Device Drivers

Before using the IC-3121, install other National Instruments software, such as application
development environments, and then install the drivers onto the device.

If you have an external USB DVD drive, you can use the external DVD drive to install the NI
Industrial Controller Device Drivers from the DVD shipped with the device. Otherwise,
complete the following steps to download and install the NI Industrial Controller Device
Drivers
1.

Connect a USB keyboard and a USB mouse to the USB ports on the IC-3121.

2.

Connect a monitor to the VGA on the IC-3121.

3.

Using the web browser on the IC-3121, navigate to 

ni.com/drivers

.

4.

In the Drivers search field, search for NI Industrial Controller Device Drivers.

5.

Download the latest version of NI Industrial Controller Device Drivers.

6.

Run the NI Industrial Controller Device Drivers installer.

Troubleshooting

The following sections provide instructions for troubleshooting the IC-3121.

IC-3121 Getting Started Guide

  | 

© National Instruments

  | 

9

Summary of Contents for IC-3121

Page 1: ...shooting 9 Where to Go Next 13 Worldwide Support and Services 13 Safety Information Caution The following paragraphs contain important safety information you must follow when installing and operating...

Page 2: ...efore returning it to service You must insulate signal connections for the maximum voltage for which the device is rated Do not exceed the maximum ratings for the device Remove power from signal lines...

Page 3: ...ibility of static electricity damage Refer to the following figures while configuring the hardware Figure 1 IC 3121 Power Connectors and Reset Button SYSTEM 12 24 V C V ISO 5 24 V 2 3 1 4 C ISO V ISO...

Page 4: ...3 0 Ports 6 44 pin Digital I O Connector Connecting the System Power Supply NI recommends the following power supply for the IC 3121 Power Supply Part Number NI PS 15 Industrial Power Supply 781093 01...

Page 5: ...lug and tighten the terminal screw to 0 2 to 0 25 N m 1 8 to 2 2 lb in of torque 5 Install the power connector plug into the SYSTEM power receptacle on the IC 3121 chassis and tighten the connector sc...

Page 6: ...ws to 0 4 N m 3 5 lb in of torque 6 Turn on the external power source Configuring the IC 3121 for NI Linux Real Time The real time version of the IC 3121 ships preloaded with NI Linux Real Time Comple...

Page 7: ...NI MAX to set a system password on the target Installing the NI Industrial Controller Device Drivers Before using the IC 3121 install the drivers onto the device Complete the following steps to instal...

Page 8: ...the IC 3121 restarts i Click Finish 8 Connect hardware to the IC 3121 The NI Industrial Controller Device Drivers enable the IC 3121 to detect any hardware connected 9 Select the target in the configu...

Page 9: ...P connection it connects to the network with a link local IP address 169 254 x x Installing the NI Industrial Controller Device Drivers Before using the IC 3121 install other National Instruments soft...

Page 10: ...rform an IP RESET The cable you are using may be inappropriate for the speed of your network causing network communication dropout While 1 000 Mbps communication over short cable lengths can be achiev...

Page 11: ...ivers on page 7 Cannot Drive Isolated Outputs Verify that you have power connected to the VISO and CISO inputs on the IC 3121 isolated power connector and that the contact at the screw terminals is so...

Page 12: ...the exception state alerting you to resolve the problem Reinstall software on the IC 3121 or contact NI for assistance Refer to the IC 3121 Getting Started Guide for information about installing soft...

Page 13: ...Factory Installation Services repairs extended warranty and other services Visit ni com register to register your NI product Product registration facilitates technical support and ensures that you rec...