FP-RLY-422
4
www.natinst.com
Relay Output Circuit
The outputs of the FP-RLY-422 consist of four independent
Form C electromechanical relays. The relays are
break-before-make, but only if you do not exceed the specified
relay operation speed. All relays remain in their power-up state or
OFF state (N.Closed connected to I.Com) until the relay (Channel)
is turned on. This will break the N.Closed–I.Com connection and
connect I.Com to N.Open. Choose the impedance of the loads so
that the current switched by any one channel is no more than 3 A.
Each relay can be controlled separately without affecting the
others, or all relays can change states at the same time.
There is an effective resistance of 100 m
Ω
between I.Com and
N.Closed or N.Open. This resistance will cause a voltage drop. For
example, if the current is 3 A, the voltage drop across the I.Com
and N.Closed or N.Open terminals is 0.3 V.
Figure 3 shows the diagram of one channel’s relay output circuit.
Figure 3.
Relay Output Circuit
N.Open
I.Com
COM
C
V
V
sup
I.Com
N.Closed