FP-AI-110 and cFP-AI-110

10

ni.com

working voltages of 250 V

rms

1

. Safety standards (such as those 

published by UL and IEC) require the use of double insulation 
between hazardous voltages and any human-accessible parts or 
circuits.

Never

 try to use any isolation product between human-accessible 

parts (such as DIN rails or monitoring stations) and circuits that 
can be at hazardous potentials under normal conditions, unless the 
product is specifically designed for such an application, as is the 
[c]FP-AI-110.

Even though the [c]FP-AI-110 is designed to handle applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system:

There is no isolation between channels on the [c]FP-AI-110. If 
a hazardous voltage is present on any channel, all channels are 
considered hazardous. Make sure that all other devices and 
circuits connected to the module are properly insulated from 
human contact.

Do 

not

 share the external supply voltages (the V and C 

terminals) with other devices (including other FieldPoint 
devices), unless those devices are isolated from human contact.

For Compact FieldPoint, you 

must

 connect the protective earth 

(PE) ground terminal on the cFP-BP-

x

 backplane to the system 

safety ground. The backplane PE ground terminal has the 
following symbol stamped beside it: 

. Connect the 

backplane PE ground terminal to the system safety ground 
using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. 
panhead screw shipped with the backplane to secure the ring 
lug to the backplane PE ground terminal.

As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes and 
commonsense practices. Mount terminal bases and backplanes 
in an area, position, or cabinet that prevents accidental or 
unauthorized access to wiring that carries hazardous voltages.

Do 

not

 use the [c]FP-AI-110 as the only isolating barrier 

between human contact and working voltages higher than 
250 V

rms

.

1  

Working voltage

 is defined as the signal voltage plus the common-mode voltage. 

Common-mode voltage

 is the voltage of the module with respect to ground.

Summary of Contents for FieldPoint FP-AI-110

Page 1: ...l Instruments FP AI 110 Manual Get Pricing Availability at ApexWaves com Call Today 1 800 915 6216 Email sales apexwaves com https www apexwaves com modular systems national instruments fieldpoint FP...

Page 2: ...nalog input module with the following features Eight analog voltage or current input channels Eight voltage input ranges 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V Three current input ranges 0 2...

Page 3: ...10 The cFP AI 110 mounts on a Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP AI 110 onto a powered backplane does not disrupt the operation of th...

Page 4: ...ions Each channel has separate input terminals for voltage VIN and current IIN input Voltage and current inputs are referenced to the COM terminals which are internally connected to each other and to...

Page 5: ...d the cFP CB x connector blocks Caution Do not connect both current and voltage inputs to the same channel Caution Cascading power between two modules defeats isolation between those modules Cascading...

Page 6: ...hannel Figure 3 FP AI 110 Analog Input Circuit Measuring Voltage with the c FP AI 110 The input ranges for voltage signals are 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V Figure 4 shows how to co...

Page 7: ...e module reads current flowing into the IIN terminal as positive and current flowing out of the terminal as negative Current flows into the IIN terminal goes through a 100 resistor and flows out from...

Page 8: ...urce with External Power Supply Input Ranges To prevent inaccurate readings choose an input range such that the signal you are measuring does not exceed either end of the range VSUP VIN V C To Analog...

Page 9: ...the rate at which the c FP AI 110 samples the inputs The c FP AI 110 resamples all of the channels at the same rate If you set all of the channels to the 50 or 60 Hz filter the c FP AI 110 samples eac...

Page 10: ...e you need and how to upgrade your firmware go to ni com info and enter fpmatrix Isolation and Safety Guidelines Caution Read the following information before attempting to connect the c FP AI 110 to...

Page 11: ...tages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact For Compact FieldPoint you must connect the protective earth PE g...

Page 12: ...ollow these guidelines if you are installing the c FP AI 110 in a potentially explosive environment Failing to follow these guidelines may result in serious injury or death Caution Do not disconnect I...

Page 13: ...an accessible circuits on the same module Caution Make sure that devices and circuits connected to the module are properly insulated from human contact Caution When terminals on the connector block ar...

Page 14: ...age 60 mV 300 mV 1 V 5 V 10 V 0 1 V 0 5 V 0 10 V 65 mV 325 mV 1 04 V 5 2 V 10 4 V 0 1 04 V 0 5 2 V 0 10 4 V 3 V 16 V 40 V 190 V 380 V 20 V 95 V 190 V 25 V 100 V 300 V 1 500 V 3 000 V 300 V 1 500 V 3 0...

Page 15: ...ut Range Typical Accuracy at 15 to 35 C of Reading of Full Scale Warranted Accuracy at 15 to 35 C of Reading of Full Scale 60 mV 0 04 0 05 0 05 0 3 300 mV 0 04 0 015 0 06 0 1 1 V 0 04 0 008 0 05 0 04...

Page 16: ...z filter 0 3 A rms Typical and warranted accuracy by temperature range Offset error drift 100 nA C Gain error drift 40 ppm C 0 1 V 0 06 0 025 0 10 0 12 0 5 V 0 07 0 007 0 11 0 03 0 10 V 0 07 0 005 0 1...

Page 17: ...ls Environmental FieldPoint modules are intended for indoor use only For outdoor use they must be mounted inside a sealed enclosure Operating temperature 40 to 70 C Storage temperature 55 to 85 C Humi...

Page 18: ...boratory use IEC 61010 1 EN 61010 1 UL 61010 1 CAN CSA C22 2 No 61010 1 For UL hazardous location and other safety certifications refer to the product label or visit ni com certification search by mod...

Page 19: ...latory compliance information To obtain the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column Mechanical...

Page 20: ...alling instructions or dial 512 795 8248 For telephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Br...

Page 21: ...o the Terms of Use section on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective...

Reviews: