background image

 

 
 

 

National Instruments FP-AI-110 Manual 

Get Pricing & Availability at 

 

ApexWaves.com 

 

Call Today: 1-800-915-6216 

Email: 

[email protected]

 

 
 

 

 

 

 

 

https://www.apexwaves.com/modular-systems/national-instruments/fieldpoint/FP-AI-110

 

Summary of Contents for FieldPoint FP-AI-110

Page 1: ...l Instruments FP AI 110 Manual Get Pricing Availability at ApexWaves com Call Today 1 800 915 6216 Email sales apexwaves com https www apexwaves com modular systems national instruments fieldpoint FP...

Page 2: ...nalog input module with the following features Eight analog voltage or current input channels Eight voltage input ranges 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V Three current input ranges 0 2...

Page 3: ...10 The cFP AI 110 mounts on a Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP AI 110 onto a powered backplane does not disrupt the operation of th...

Page 4: ...ions Each channel has separate input terminals for voltage VIN and current IIN input Voltage and current inputs are referenced to the COM terminals which are internally connected to each other and to...

Page 5: ...d the cFP CB x connector blocks Caution Do not connect both current and voltage inputs to the same channel Caution Cascading power between two modules defeats isolation between those modules Cascading...

Page 6: ...hannel Figure 3 FP AI 110 Analog Input Circuit Measuring Voltage with the c FP AI 110 The input ranges for voltage signals are 0 1 V 0 5 V 0 10 V 60 mV 300 mV 1 V 5 V and 10 V Figure 4 shows how to co...

Page 7: ...e module reads current flowing into the IIN terminal as positive and current flowing out of the terminal as negative Current flows into the IIN terminal goes through a 100 resistor and flows out from...

Page 8: ...urce with External Power Supply Input Ranges To prevent inaccurate readings choose an input range such that the signal you are measuring does not exceed either end of the range VSUP VIN V C To Analog...

Page 9: ...the rate at which the c FP AI 110 samples the inputs The c FP AI 110 resamples all of the channels at the same rate If you set all of the channels to the 50 or 60 Hz filter the c FP AI 110 samples eac...

Page 10: ...e you need and how to upgrade your firmware go to ni com info and enter fpmatrix Isolation and Safety Guidelines Caution Read the following information before attempting to connect the c FP AI 110 to...

Page 11: ...tages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact For Compact FieldPoint you must connect the protective earth PE g...

Page 12: ...ollow these guidelines if you are installing the c FP AI 110 in a potentially explosive environment Failing to follow these guidelines may result in serious injury or death Caution Do not disconnect I...

Page 13: ...an accessible circuits on the same module Caution Make sure that devices and circuits connected to the module are properly insulated from human contact Caution When terminals on the connector block ar...

Page 14: ...age 60 mV 300 mV 1 V 5 V 10 V 0 1 V 0 5 V 0 10 V 65 mV 325 mV 1 04 V 5 2 V 10 4 V 0 1 04 V 0 5 2 V 0 10 4 V 3 V 16 V 40 V 190 V 380 V 20 V 95 V 190 V 25 V 100 V 300 V 1 500 V 3 000 V 300 V 1 500 V 3 0...

Page 15: ...ut Range Typical Accuracy at 15 to 35 C of Reading of Full Scale Warranted Accuracy at 15 to 35 C of Reading of Full Scale 60 mV 0 04 0 05 0 05 0 3 300 mV 0 04 0 015 0 06 0 1 1 V 0 04 0 008 0 05 0 04...

Page 16: ...z filter 0 3 A rms Typical and warranted accuracy by temperature range Offset error drift 100 nA C Gain error drift 40 ppm C 0 1 V 0 06 0 025 0 10 0 12 0 5 V 0 07 0 007 0 11 0 03 0 10 V 0 07 0 005 0 1...

Page 17: ...ls Environmental FieldPoint modules are intended for indoor use only For outdoor use they must be mounted inside a sealed enclosure Operating temperature 40 to 70 C Storage temperature 55 to 85 C Humi...

Page 18: ...boratory use IEC 61010 1 EN 61010 1 UL 61010 1 CAN CSA C22 2 No 61010 1 For UL hazardous location and other safety certifications refer to the product label or visit ni com certification search by mod...

Page 19: ...latory compliance information To obtain the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column Mechanical...

Page 20: ...alling instructions or dial 512 795 8248 For telephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Br...

Page 21: ...o the Terms of Use section on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective...

Reviews: