background image

4

Figure 4.  

RS-232 Connector Pinout

Up to 24 additional FP-1001 network modules can be connected to 
this FP-1000 module by using the built in RS-485 repeater. This 
repeater makes the RS-485 port of the FP-1000 appear to the 
additional FP-1001 modules as if it were an RS-485 port of the host 
computer. The pinout of the RS-485 connector is shown in 
Figure 5. 

Figure 5.  

RS-485 Connector Pinout

The TX+ of the FP-1000 must be connected to the RX+ of all of the 
FP-1001 modules, and the TX- of the FP-1000 must be connected 
to the RX- of all of the FP-1001 modules. This pair of connections 
provides communication from the host computer, through the 
FP-1000, to the FP-1001 modules.

The RX+ of the FP-1000 must be connected to the TX+ of all of the 
FP-1001 modules, and the RX- of the FP-1000 must be connected 
to the TX- of all of the FP-1001 modules. This pair of connections 
provides communication to the host computer, through the 
FP-1000, from the FP-1001 modules.

GND

NC

RX

TX

NC

RTS

NC

DSR

NC

5

4

3

2

1

9

8

7

6

NC = Not Connected

GND = Ground

RX = Recieve

TX = Transmit

RTS = Request to Send

DSR = Data Set Ready

Legend:

RX–

RX+

TX–

TX+

GND

1

2

3

4

5

FP1000.fm  Page 4  Thursday, July 31, 1997  8:49 AM

Summary of Contents for FieldPoint FP-1000

Page 1: ...in high efficiency power supply powers I O modules 40 to 70 C operation Overview The FP 1000 is a network module for the FieldPoint system It provides connection to an RS 232 network using a simple A...

Page 2: ...teps 1 With a flat bladed screwdriver open the rail clip to the unlocked position as shown in Figure 1 Figure 1 DIN Rail Clip 2 Hook the lip on the rear of the FP 1000 onto the top of a 35 mm DIN rail...

Page 3: ...installed FP 1000 network module Figure 3 Installed Network Module Network Connection Connect the FP 1000 to a host computer using the 9 position DSub RS 232 connector on the FP 1000 Connect the RS 2...

Page 4: ...01 modules and the TX of the FP 1000 must be connected to the RX of all of the FP 1001 modules This pair of connections provides communication from the host computer through the FP 1000 to the FP 1001...

Page 5: ...dule Switches 1 5 set the network address and switches 6 8 set the baud rate Every network module connected to one serial port of the host computer must be given a unique address however modules on di...

Page 6: ...k Address Switch Settings Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address Decimal 0 130 10 140 20 150 30 160 40 170 50 180 60 190 1 2 3 4 5 6 7 8 1 2 3...

Page 7: ...ud Rate 300 19200 1200 38400 2400 57600 9600 115200 Table 1 Network Address Switch Settings Continued Switch Positions 1 5 Network Module Address Decimal Switch Positions 1 5 Network Module Address De...

Page 8: ...inals provided on each terminal base for such power supply connections The power connector is a 4 pin screw terminal connector whose pinout is shown in Figure 8 Figure 8 FP 1000 and FP 1001 Power Conn...

Page 9: ...ational Power Consumption 1 W 1 15 I O module power requirements Operating Temperature 40 C to 70 C Storage Temperature 55 C to 100 C Relative Humidity 5 to 90 non condensing Weight 250 g 8 7 oz CE Ma...

Page 10: ...10 Mechanical Dimensions Figure 9 shows the mechanical dimensions of the FP 1000 Figure 9 Mechanical Dimensions 4 31 109 5 3 58 90 9 4 19 106 4...

Page 11: ......

Page 12: ......

Reviews: