![National Instruments FieldPoint cFP-DI-304 Operating Instructions Manual Download Page 2](http://html1.mh-extra.com/html/national-instruments/fieldpoint-cfp-di-304/fieldpoint-cfp-di-304_operating-instructions-manual_709170002.webp)
FieldPoint
™
Operating Instructions
cFP-DI-304
32-Channel, 24 VDC Sinking Digital Input Module
These operating instructions describe how to install and use
the cFP-DI-304 digital input module. For information about
configuring and accessing the cFP-DI-304 over a network, refer to
the user manual for the FieldPoint network module you are using.
Features
The cFP-DI-304 is a FieldPoint digital input module with the
following features:
•
32 sinking digital input channels
•
Compatible with 24 VDC sourcing-output devices
•
Inputs protected up to 30 VDC (up to 60 VDC on up to
eight channels)
•
250 V
rms
CAT II continuous channel-to-ground isolation,
verified by 2,300 V
rms
, 5 s dielectric withstand test
•
On/off LED indicators
•
Hot swappable
Installing the cFP-DI-304
The cFP-DI-304 mounts on a Compact FieldPoint backplane
(cFP-BP-
x
), which provides operating power to the module.
Installing the cFP-DI-304 onto a powered backplane does not
disrupt the operation of the FieldPoint bank.
To install the cFP-DI-304, refer to Figure 1 and complete the
following steps:
1. Align the captive screws on the cFP-DI-304 with the holes on
the backplane. The alignment keys on the cFP-DI-304 prevent
backward insertion.
2. Press firmly to seat the cFP-DI-304 on the backplane.