5
cFP-CB-1/2/3/4
2. Verify that there are no cuts in the wire insulation that can
cause a safety hazard.
3. Strip 6 mm (0.24 in.) of insulation from the ends of the wires.
4. Insert the entire stripped ends of the wires into the appropriate
screw terminals. Do not allow any bare wire to show outside
the screw terminals.
5. Using a 1/8 in. flathead screwdriver, tighten the screw
terminals to 0.5–0.6 N
⋅
m (4.4–5.3 lb
⋅
in.) of torque.
Wiring to the cFP-CB-2
You need a flathead screwdriver with a blade smaller than
2.3 × 1.0 mm (0.09 × 0.04 in.) to connect wires to the detachable
spring-terminal connector. Complete the following steps:
1. Verify that there are no cuts in the wire insulation that can
cause a safety hazard.
2. Strip 7 mm (0.28 in.) of insulation from the ends of the wires.
3. Insert the screwdriver into a spring clamp activation slot.
4. Insert the entire stripped end of the wire into the corresponding
spring terminal. Do not allow any bare wire to show outside the
terminal.
5. Remove the screwdriver to clamp the wire into the terminal.
Figure 6.
Connecting a Wire to the Spring-Terminal Connector of the cFP-CB-2
6. When the wiring is complete, insert the connector into the
cFP-CB-2.