© National Instruments
|
1-19
The wire should be 1.31 mm
2
(16 AWG) or larger solid copper wire with a maximum length of
1.5 m (5 ft). Attach the wire to the earth ground of the facility’s power system. For more
information about earth ground connections, refer to the KnowledgeBase document,
Grounding
for Test and Measurement Devices
and entering the Info Code
emcground
.
Note
If you use shielded cabling to connect to a C Series module with a plastic
connector, you must attach the cable shield to the chassis grounding terminal using
1.31 mm
2
(16 AWG) or larger wire. Use shorter wire for better EMC performance.
Cables and Accessories
Table 1-5 contains information about cables and accessories available for the cDAQ chassis. For
a complete list of cDAQ chassis accessories and ordering information, refer to the pricing
section of the NI cDAQ-9188XT product page at
Table 1-5.
Cables and Accessories
Accessory
Part Number
NI PS-15 power supply (24 VDC, 5 A,
100 to 120/200 to 240 VAC input, -25 to 70 °C)
781093-01
NI PS-9 desktop power supply
(12 VDC, 1.25 A, 100 to 240 VAC input, 0 to 70 °C, derated
0.27 W/°C above 40 °C)
780703-01
NI 9901 desktop mounting kit
779473-01
NI 9905 panel mount kit
779558-01
NI 9915 DIN rail mounting kit
779018-01
2-pos screw terminal kit for power supply connection, qty 4
780702-01
CAT-5E Ethernet cable, shielded, (2 m, 5 m, and 10 m lengths)
151733-02/05/10