National Instruments 9470 Getting Started Manual Download Page 1

GETTING STARTED GUIDE

NI 9470

5 V DC to 30 V DC, 8-Channel (Sourcing
Output), 2 kHz C Series Digital Module

Summary of Contents for 9470

Page 1: ...GETTING STARTED GUIDE NI 9470 5 V DC to 30 V DC 8 Channel Sourcing Output 2 kHz C Series Digital Module ...

Page 2: ...uidelines in this document are specific to the NI 9470 The other components in the system might not meet the same safety ratings Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Related Documentation For more information about the NI 9470 read the following documents on ni com manuals NI 9470 Safety Environmental and Regulato...

Page 3: ...e on ni com Table 1 NI 9470 Cables and Accessories Cable Accessory Part Number 1 M Cable 132410A 01 2 M Cable 132410A 02 5 M Cable 132410A 05 If you would like to build your own cables for the NI 9470 you will need to purchase the following crimp tools or their equivalents Refer to the manufacturer s documentation on molex com for more information on building your own cables NI 9470 Getting Starte...

Page 4: ...and Crimp Tool for Ultra Fit Tang less Crimp Terminals 16 18 AWG UL1061 Wires 2002184600 18 AWG to 16 AWG In addition to the provided connector housings you will need the following parts for each cable The Ultra Fit housing leaves the crimps exposed at the rear of the housing NI recommends insulating the back of the connector with 25 mm 1 0 in diameter heat shrink 4 ni com NI 9470 Getting Started ...

Page 5: ... Wire AWG Quantity Ultra Fit Tangless Crimp Terminal Female 0 76µm Gold Au Plating 20 22 AWG 1722536112 22 AWG to 20 AWG 16 Ultra Fit Tangless Crimp Terminal Female 0 76µm Gold Au Plating 16 18 AWG 1722536012 18 AWG to 16 AWG 16 NI 9470 Getting Started Guide National Instruments 5 ...

Page 6: ...3 Vsup4 Vsup5 Vsup6 Vsup7 COM COM COM COM COM COM COM DO0 DO0 DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO1 DO2 DO3 DO4 DO5 DO6 DO7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 6 ni com NI 9470 Getting Started Guide ...

Page 7: ...Common reference connection for the power supply DO Digital output return negative connection DO Digital output source positive connection Vsup DC voltage power supply connection NI 9470 Block Diagram NI 9470 Getting Started Guide National Instruments 7 ...

Page 8: ...t a variety of industrial devices such as solenoids valves motors actuators relays and lamps to the NI 9470 Connect the device between the DO and DO pins and connect the external power supply Use cables 20 m or shorter for connections from DO and DO to the load 8 ni com NI 9470 Getting Started Guide ...

Page 9: ...m your system if any external power supplies connected to the Vsup and COM pins are powered on Attention Ne pas installer ou retirer les modules de la Série C de votre système si une alimentation externe connectée aux broches Vsup et COM est sous tension Complete the following steps to connect an external power supply to the NI 9470 Use cables 10 m or shorter for connections from Vsup to COM to th...

Page 10: ...t protection Each Vsup terminal has reverse polarity protection Notice Voltages greater than the supply voltage and negative voltage conditions on DO can damage the NI 9470 Notice The DO terminal is not protected against overvoltage conditions Note Refer to the NI 9470 Datasheet on ni com manuals for maximum continuous output current short circuit behavior and short circuit trip time specification...

Page 11: ...n of Conformity DoC for additional regulatory compliance information To obtain product certifications and the DoC for NI products visit ni com product certifications search by model number and click the appropriate link NI 9470 Getting Started Guide National Instruments 11 ...

Page 12: ...eries Documentation Resources ni com info cseriesdoc Services ni com services NI 9470 Datasheet NI RIO Help LabVIEW FPGA Help NI 9470 Datasheet NI DAQmx Help LabVIEW Help Installs with the software Located at ni com manuals 12 ni com NI 9470 Getting Started Guide ...

Page 13: ...duct registration facilitates technical support and ensures that you receive important information updates from NI NI corporate headquarters is located at 11500 North Mopac Expressway Austin Texas 78759 3504 NI also has offices located around the world For support in the United States create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For support outside the United State...

Page 14: ...ents EULAs and third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain relevant HTS codes ECCNs and other import export data NI MAKES NO EXPRESS OR IMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINED HEREIN AND SHALL NOT BE LIABLE FOR ANY ...