Caution
Do not disconnect I/O-side wires or
connectors unless power has been switched off or the
area is known to be nonhazardous.
Caution
Do not remove modules unless power has
been switched off or the area is known to be
nonhazardous.
Caution
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Division 2 and Zone 2 applications,
install the system in an enclosure rated to at least IP54
as defined by IEC/EN 60079-15.
Caution
For Division 2 and Zone 2 applications,
connected signals must be within the following limits.
Capacitance
0.2 µF max
Special Conditions for Hazardous Locations Use in
Europe and Internationally
The NI 9401 has been evaluated as Ex nA IIC T4 Gc equipment
under DEMKO Certificate No. 03 ATEX 0324020X and is
IECEx UL 14.0089X certified. Each NI 9401 is marked II 3G
NI 9401 Getting Started Guide
|