background image

6

 Electric Heat Kit Installation Instructions

FIG. 1

Electric Heat Kit P Series MCA/MOP Data

Table 1

Heat Kit

Model

Air Handler 

Model

(kW) Electric Heat

MIN Circuit Ampacity

MAX Fuse or Breaker

(HACR) Ampacity

208

240

208

240

EHK3-05B

24

5.0

23.9

27.3

25

30

EHK3-08B

7.5

35.1

40.4

40

45

EHK3-10B

10

44.6

51.3

45

60

EHK3-05B

36

5

24.9

28.3

25

30

EHK3-08B

7.5

36.1

41.4

40

45

EHK3-10B

10

45.6

52.3

50

60

Fan Coil Unit Size - Mimimum CFM*

Fan Coil Unit Size - Mimimum CFM*

Electric Heater Part Number

Units Sizes Used With 

kW

18

24

30

36

EHK3-05B

24-36

5

325

450

575

700

EHK3-08B

24-36

7.5

350

475

600

725

EHK3-10B

24-36

10

375

500

625

750

* - Simultaneous electric heat and heat pump operation may require higher cfm or fan speed if applicable.