National Comfort Products MADISON 1000 SERIES Installation Instructions Manual Download Page 14

National Comfort Products

539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579

LIMITED EXTENDED PROTECTION WARRANTY

FOR

NATIONAL COMFORT PRODUCTS (NCP) BENSALEM, PA

SPLIT-SYSTEM CONDENSING UNITS

This NCP product is warranted to be free from all manufacturing defects, material or workmanship, for a period of one year from 

the date of installation (receipt required), whether or not actual use begins on this date, or one year from the date of manufacture 

if the date of installation cannot be verified. Immediate notice to NCP will (A) provide a new or remanufactured part to replace the 

defective part, without charge for the part itself, or (B) provide a replacement unit.

National Comfort Products will not be responsible for: local transportation, removing, related service, labor, diagnosis calls, 

refrigerant, costs incurred for returning defective parts, damage or repairs required due to faulty installation or improper 

application by others, damage as a result of fire, wind, floods, lightning, accidents, or corrosive atmosphere.

EXTENDED 2ND THRU 5TH YEAR COMPRESSOR WARRANTY

If the compressor should fail because of a manufacturing defect, is in the original installation, has been operated under normal 

conditions, and is in the 2nd to 5th year following the above determined date, NCP will provide, at its option, a new or remanufac

-

tured replacement compressor.

Replacement parts are warranted for the remainder of the original product warranty, or for one year, whichever is longer. 

NCP may require that defective parts be returned to verify and identify the cause of the defect.

LIMITATION OF WARRANTIES — ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES 

OF MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH EACH 

LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN 

IMPLIED  WARRANTY  LASTS,  SO THE ABOVE  LIMITATIONS  MAY  NOT APPLY TO YOU. THE  EX

-

PRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, 

ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER.  

MATERIAL IS INSPECTED AT THE FACTORY AND RELEASED TO TRANSPORTATION AGENCY IN 

GOOD CONDITION.  WHEN RECEIVED, VISUAL INSPECTION MUST BE MADE IMMEDIATELY.  AP

-

PARENT SHIPPING DAMAGE SHOULD BE NOTED ON THE DELIVERY RECEIPT AND THE MATERI

-

AL INSPECTED IN THE PRESENCE OF THE CARRIER’S REPRESENTATIVE.  IF DAMAGE IS FOUND 

A CLAIM MUST BE FILED WITH THE CARRIER IMMEDIATELY.

FREIGHT DAMAGE IS NOT COVERED UNDER THIS WARRANTY.

WARNING: NO WARRANTY ON NEW UNITS INSTALLED BEHIND BRICK FACADES.  IN YEARS PAST, 

IT WAS COMMON PRACTICE TO ADD A BRICK PATTERN FACADE (PIGEON HOLES) IN FRONT OF 

THE THRU-THE-WALL UNIT TO CHANGE THE EXTERIOR APPEARANCE OF THE BUILDING.  ALL 

OBSTACLES ADDED TO IMPEDE AIR FLOW OF THE CONDENSING UNIT WILL DECREASE PER

-

FORMANCE AND CAUSE PREMATURE EQUIPMENT FAILURE AND VOID ALL WARRANTIES.  CON

-

SULT FACTORY WITH ANY QUESTIONS.

This warranty gives you specific legal rights. You may also have rights which vary from state to state.

NATIONAL COMFORT PRODUCTS, BENSALEM, PENNSYLVANIA

 

NOTE: 

All warranty parts and paper work must be submitted no later than 60 days after failure.  

Warranty requests submitted after 60 days of failure will not be processed.

14

Summary of Contents for MADISON 1000 SERIES

Page 1: ...eve and the wall Completely fill the clearance between the unit and the wall sleeve with a polyurethane foam sealant Fol low manufacturer s suggested application manual During periods of rain and wind the primary drainage path 4 may not be adequate to handle the load Secondary pre cautions may also be required but not limited to the follow ing a Seal flashing to unit b Floor drain c Additional fie...

Page 2: ...r drier must be installed SPORLAN 083 S or similar The unit has internally mounted service valves Field tub 1 ing may be routed through the locations provided in either the top or rear flange Care should be taken not to block ac cess to internal components Seal unused knockouts with high grade sealant Gaskets are provided for liquid and suction lines NOTE Always use refrigeration grade copper tubi...

Page 3: ...e alloy is used Step 5 This is not a back seating valve To open the valve re move the valve cap with an adjustable wrench Insert a 3 16 or 5 16 hex wrench into the stem Back out counter clockwise until the valve stem just touches the retaining ring Step 2 Wrap a wet rag around the copper stub before brazing Step 4 After brazing quench with a wet rag to cool the joint and remove any flux residue Ev...

Page 4: ...uce refrigerant into the system NOTE Oil charge is polyester 32bce Step 4 Evacuation Step 5 Refrigerant Charging When the correct refrigerant charge level is obtained re 3 move the manifold gauge set Replace the gauge port caps 4 Permanently stamp the unit data plate with the total amount of refrigerant in the system For coils equipped with TXV s charge to sub cooling 12 16 at ser vice valve super...

Page 5: ...rioration Sequence of Operations for Madison Avenue Option Step 7 Maintenance The compressor crankcase heater will be energized as long as there is power to the unit The high pressure switch HPS and low pressure switch LPS will be closed as long as refrigerant pressure in the condensing unit is normal Upon a call for cooling as indicated by 24 vac being applied to low voltage connections C and Y C...

Page 6: ...Figure 2 Wiring Schematic NCPC 6 ...

Page 7: ...7 Figure 3 Wiring Schematic Madison Series ...

Page 8: ... 208 230 60 1 12 14 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 6 5 43 8 0 43 10 6 54 RLA Amps LRA Amps FAN MOTOR 0 25 1140 1 2 0 25 1140 1 2 0 25 1140 1 2 HP RPM Amps Full Load COIL 3 46 16 3 46 16 3 46 16 Face Area FPI Service Clearance 30 4 7 8 18 1 2 28 21 32 2 19 32 15 16 2 3 32 1 17 32 2 7 8 1 17 32 2 15 16 1 3 8 2 1000 SERIES 8 13 32 1 15 32 7 8 13 19 32 19 7 8 ...

Page 9: ...0 2 15 208 230 60 1 12 14 4 20 208 230 60 1 12 17 3 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 6 5 43 8 0 43 10 6 54 RLA Amps LRA Amps FAN MOTOR 0 25 1140 1 2 0 25 1140 1 2 0 25 1140 1 2 HP RPM Amps Full Load COIL 3 77 16 3 77 16 3 77 16 Face Area FPI Service Clearance 30 3 17 32 7 8 1 17 32 1 3 8 1 17 32 18 1 2 32 20 5 16 7 8 1 3 8 23 3 4 1 1 2 7 8 1 5 16 3 5 16 5 13 1...

Page 10: ...SIONS 29 1 2 23 18 1 2 3 8 3 4 29 1 2 23 18 1 2 3 8 3 4 29 1 2 23 18 1 2 3 8 3 4 Width Height Length Liquid Valve Vapor Valve NOMINAL CAPACITY B HR 18 000 23 600 28 500 ELECTRICAL 208 230 60 1 14 10 2 15 208 230 60 1 12 14 4 20 208 230 60 1 12 14 8 25 Volts Hertz Phase Min AWG Wire Min Cir Ampacity Max Fuse COMPRESSOR 6 5 43 8 0 43 10 6 54 RLA Amps LRA Amps FAN MOTOR 0 25 1140 1 2 0 25 1140 1 2 0 ...

Page 11: ...38 14270038 14267007 14214013 14214021 14256933X 14256936Y 14256939S 14208360 14270038 14270036 14267007 14214013 14214021 14256933X 14256936Y 14256939S 14208360 14270038 14270036 14267007 14214013 14214021 14256933X 14256936Y 14256939S ITEM DESCRIPTION NCPC 418 NCPC 424 NCPC 430 16 17 18 19 19a 20 Right Side Panel Left Side Panel Wire Grille 1000 Muffler MADISON Touch Up Paint 14256938S 14256937S...

Page 12: ...0 Blower Housing Inlet Ring 2 req d Motor Blower Mount Access Panel 3000 Top Panel 3000 14208356 14270038 14270038 14267007 14214013 14214021 14256933X 14256969S 14256967S 14208357 14270038 14270036 14267007 14214013 14214021 14256933X 14256969S 14256967S 14208357 14270038 14270036 14267007 14214013 14214021 14256933X 14256969S 14256967S ITEM DESCRIPTION NCPC 418 NCPC 424 NCPC 430 16 17 18 19 19a ...

Page 13: ...eel 7 6 OD x 8 0 Blower Housing Inlet Ring 2 req d Motor Blower Mount Access Panel 4000 Top Panel 4000 14208359 14270038 14270038 14267007 14214013 14214021 14256933X 14256970S 14256968S 14208358 14270038 14270036 14267007 14214013 14214021 14256933X 14256970S 14256968S 14208358 14270038 14270036 14267007 14214013 14214021 14256933X 14256970S 14256968S ITEM DESCRIPTION NCPC 418 NCPC 424 NCPC 430 1...

Page 14: ...require that defective parts be returned to verify and identify the cause of the defect LIMITATION OF WARRANTIES ALL IMPLIED WARRANTIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU THE EX PR...

Page 15: ... have to wait for a replacement compressor to be shipped from Bensalem PA The situation may present itself where it is better for the compressor to be returned to National Comfort Products during the 20 month Bristol warranty period NCP will also honor the Bristol 20 month warranty period All returned compressors must have the tubing connections closed with rubber plugs or brazed shut National Com...

Page 16: ...seamless rifled copper tubes CABINET Unit cabinet shall be constructed of heavy gauge galvanized or aluminized steel The steel shall be treated by phosphate washes prior to electrostatically applied and oven baked paint FACTORY CHARGED Each unit shall be charged with R410a for proper operation with recommended indoor coil and 10 foot tubing SERVICE VALVES Each unit shall be equipped with liquid an...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...R 410a Split System Condensing Unit Installation Instructions Rev 09 10 PLEASE NOTE ALL 2 5 TON UNITS 430 MODELS HAVE BEEN DISCONTINUED ...

Reviews: