Parameter
Default
Description
1
2
3
4
5
6
Delta control
p = XXX.X [bar]
0.1
This parameter communicates by how much the measured
value must fall in relation to the set value so that the pump,
during shutdown in control ramp, is restarted.
3
4
5
6
bar
1
2
sec
Hz
1: Min motor frequency; 2: Frequency min control; 3: Delta
control; 4: Set value ; 5: Stop delay; 6: Control ramp
x
x
Delta stop
p = XX.X [bar]
0.5
This parameter represents the increment of the measured val-
ue with respect to the set value that must be exceeded so that
a forced shutdown of the pump according to the stop ramp can
occur.
x
x
Ki
XXX
Integral coefficient used in constant value adjustment.
x
x
x
Kp
XXX
Proportional coefficient used in constant value adjustment.
x
x
x
COMBO
ON/OFF
OFF
Enable the function COMBO for the combined operation of
several pumps in parallel. Read the dedicated chapter.
x
x
x
Address
XX
01
Device address when in COMBO mode:
• 0: master
• 01 to 07: slave
x
x
x
Alternance
ON/OFF
ON
Enabling the alternation between units in COMBO and D.O.L.
The order of priority of operation is alternated based on the
previous start-up of each pump in order to obtain an almost
uniform wear of the pumps.
x
x
x
Alternance period
t = XX [h]
0
Maximum difference in operating hours between multiple devi-
ces in the unit.
0 means 5 minutes.
x
x
x
COMBO synchrony
ON/OFF
OFF
Through this parameter it is possible to activate the synchro-
nous operation of the pumps in COMBO. Read the dedicated
chapter.
However, it is necessary to lower parameter Frequency min
controlaccordingly.
x
x
Start delay AUX
t = XX [s]
00
Time delay with which the pumps in a group start up after
the variable speed pump has reached the maximum motor
frequency and the measured value has fallen below the differ-
ence Set value - Delta control.
x
x
x
PI control
Direct/Reverse
Direct
PI control mode:
• Direct: as the pump speed increases, the measured value
increases.
• Reverse: as the pump speed increases, the measured value
decreases.
x
x
Periodic autorun
t = XX [h]
00
Periodic pump start-up after X hours of inactivity. The value 0
disables the function.
x
x
x
x
x
Dry run cosphi
cosphi = X.XX
x
x
x
x
x
x
Restarts delay
t = XX [min]
10
Time base that establishes the delay of attempts to restart the
pump following a no-water alarm. With each attempt, the delay
time is doubled. The maximum number of attempts is 5.
x
x
x
x
x
x
Change password1
Press ENT
By pressing the ENT key it is possible to change the installer
level password (level 1) (default 001).
x
x
x
x
x
x
SUND