5.1.2 Programming
Parameters are organized in four main menus: CONTROL, MOTOR, IN/OUT, CONNECT.
Parameters are password protected in 2 levels of access:
Installer level (CONTROL, IN/OUT). Password: 001
Advanced level (MOTOR, CONNECT). Password: 002
IN/OUT PARAMETERS
Parameter
Default
Description
bar
Unit [bar,%,ft,in,cm,m,K,F,C,gpm,l/min,m3/h,atm,psi]
16
Sensor full scale.
0
Sensor minimum value.
20%
Zero correction for analog input 1 (4-20 mA)
(20 mA x 20% = 4 mA).
20%
Zero correction for analog input 2 (4-20 mA)
(20 mA x 20% = 4 mA).
0%
Zero correction for analog input 3 (0-10V)
(10V x 00% = 0 V).
0%
Zero correction for analog input 4 (0-10V)
(10V x 00% = 0 V).
Independent
Function logic for analog input AN1,AN2 (independent, lower value,
higher value, difference 1-2).
N.O.
By selecting N.O. (normally open) the inverter runs the motor if the
digital input 1 is open; motor will be stopped if the digital input 1 is
closed. By selecting N.C. (normally closed) the inverter runs the motor
if the digital input 1 is closed; motor will be stopped if the digital input 1
is opened.
N.O.
By selecting N.O. (normally open) the inverter runs the motor if the
digital input 2 is open; motor will be stopped if the digital input 2 is
closed. By selecting N.C. (normally closed) the inverter runs the motor
if the digital input 2 is closed; motor will be stopped if the digital input 2
is opened.
Unit
XXXXX
F. scale sensor
XXX.X
Min.value sensor
XXX.X
Offset input 1
[%]
Offset input 2
[%]
Offset input 3
[%]
Offset input 4
[%]
AN1,AN2 function
XXXXXX
Digital input 1
N.O. / N.C
.
Digital input 2
N.O. / N.C.